Parameter
Description
Opt. pump starts /h
3-6-1
Entering the optimal pump starts per hour.
The pump runtime is automatically
adapted
Min. run time
3-6-2
Limit for minimum runtime of pump
Min. run time corr.
3-6-3
Correction value for minimum runtime of
pump
Max. run time
3-6-4
Maximum pump runtime.
After the time has lapsed, the system
switches over to the next pump.
Start delay
3-6-5
Start delay of pumps if pressure remains
below setpoint
Stop delay
3-6-6
Stop delay of pumps if pressure remains at
setpoint
RDP delay
3-6-8
Stop delay following detection of dry
running occurrence
High/low alarm delay
3-6-9
Time window for suppressing alerts when
system pressure is exceeded/undershot
WSD 1 pulse length
3-6-10
Water flow detection 1, length of pulse in
seconds
WSD 2 pulse length
3-6-11
Water flow detection 2, length of pulse in
seconds
WSD 3 pulse length
3-6-12
Water flow detection 3, length of pulse in
seconds
Sys. start up delay
3-6-13
Start delay following re-start
Jockey min. run time
3-6-14
Limit for minimum runtime of jockey pump
Time/Date
3-7
Date and time
Date
3-7-1
Setting the date
Year
3-7-1.1.1
Setting the year
Factory setting
Possible settings
10
0.. 99
180
0.. 999
10
0.. 99
86400
0.. 604800
1
0.. 999
1
0.. 999
10
0.. 999
60
10.. 999
4
0.. 99
4
0.. 99
4
0.. 99
10
0.. 32
0
0.. 999
-
-
-
-
...
1970.. 2099
min. value
max. value
Read access right Write access right
0
99
Everybody
0
999
Everybody
0
99
Everybody
0
604800
Everybody
0
999
Everybody
0
999
Everybody
0
999
Everybody
10
999
Everybody
0
99
Everybody
0
99
Everybody
0
99
Everybody
0
32
Service
0
999
Service
-
-
Everybody
-
-
Everybody
1970
2099
Everybody
Service
Customer
Service
Service
Service
Service
Service
Service
Service
Service
Service
Service
Service
Nobody
Customer
Customer