Table 18: Access level parameter
Parameter
Description
3-2-1-1
Enter customer password for
access
Enter service password for access
Change customer access level
password
Password-protected access level
for customer parameter
Customer access level You must enter the password under (3-2-1-1) Login to gain access. The password can
Service access level You must enter a password under Service Login.
Example Parameter 3-5-1 Setpoint
6 Operation
Table 17: Access levels
Access level
Standard (no login)
Customer
Service
If a parameter's access level is not explicitly specified, the parameter is always
assigned the customer access level.
Possible setting
0000...9999
0000...9999
0000...9999
Disabled
Enabled
Entering the password
be changed under Customer Password after entering "7353" (factory password). If
password protection is deactivated via parameter 3-2-1-2, the customer access level
becomes the standard access level. This applies to the factory settings.
NOTE
If no keys are pressed for ten minutes, the system will automatically return to the
standard access level.
6.1.3.3.3 Displaying and changing parameters
The parameter numbers contain the navigation path, which helps you find a
particular parameter quickly and easily. The first digit of the parameter number
indicates the first menu level, which is called up directly via the four menu keys.
Table 19: Assignment of menu keys
Key
Menu
Operation
Diagnosis
Settings
Information
Subsequent steps are carried out via the navigation keys.
1. First digit of parameter number: 3-5-1
Press the "Settings" menu key.
ð 3-1 appears in the top left of the screen.
2. Second digit of parameter number: 3-5-1
Press the arrow key to change the display 3-1 on the screen (upper left) to 3-5.
BoosterControl Advanced
Description
Access without password entry.
Access level for the expert user with
access to all parameters required for
commissioning.
Access level for service personnel.
Access level required
Standard
Service
Customer
Customer
Factory
setting
0000
-
-
Disabled
25 of 88
Need help?
Do you have a question about the BoosterControl Advanced and is the answer not in the manual?
Questions and answers