Setting Table - ABB REC 561 User Manual

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
IN:
DREP-INPUT36
DREP-INPUT37
DREP-INPUT38
DREP-INPUT39
DREP-INPUT40
DREP-INPUT41
DREP-INPUT42
DREP-INPUT43
DREP-INPUT44
DREP-INPUT45
DREP-INPUT46
DREP-INPUT47
DREP-INPUT48
OUT:
DREP-OFF
DREP-RECSTART
DREP-CLEARED
DREP-RECMADE
DREP-MEMUSED

4.2 Setting table

PARAMETER:
Disturbance Report:
Operation
RecordingTimes:
tLim
tPost
tPre
Binary/Input 1 - 48:
TrigOperation
TrigLevel
Disturbance report - Settings
DESCRIPTION:
Binary signal to be recorded as signal No. 36
Binary signal to be recorded as signal No. 37
Binary signal to be recorded as signal No. 38
Binary signal to be recorded as signal No. 39
Binary signal to be recorded as signal No. 40
Binary signal to be recorded as signal No. 41
Binary signal to be recorded as signal No. 42
Binary signal to be recorded as signal No. 43
Binary signal to be recorded as signal No. 44
Binary signal to be recorded as signal No. 45
Binary signal to be recorded as signal No. 46
Binary signal to be recorded as signal No. 47
Binary signal to be recorded as signal No. 48
DESCRIPTION:
Disturbance Report operation during normal
condition is set to Off
Disturbance recording started
All disturbances in the Disturbance Report
cleared
Disturbance recording made and stored in flash
memory
Disturbance Recorder memory capacity utilized
to 80%
SETTING RANGE:
On, Off
(0.5 - 4.0) s
(0.1 - 3.0) s
(0.05 - 0.30) s
Off, On
Trig on 1, Trig on 0
DESCRIPTION:
Operation of the whole Disturbance Report
Pre-fault recording time
Post-fault recording time
Limit time
On=the signal is used for trigering,
Off=the signal is not used for triggering
Trig level for the binary signal
1MRK 580 133-XEN