7.2.8 SWICONA
Apparatus control
Table 15: Input signals for SWICONA
IN:
SAxx-POSIND_V
SAxx-POS_L1_O
SAxx-POS_L2_O
SAxx-POS_L3_O
SAxx-POS_L1_C
SAxx-POS_L2_C
SAxx-POS_L3_C
SAxx-BLK_UPD
SAxx-PROC_UPD
SAxx-MA_UPD_O
SAxx-MA_UPD_C
SAxx-UPD_BLK
SAxx-SELECT
SAxx-FDB_SEL
SAxx-OPEN
SAxx-CLOSE
SAxx-AU_OP_V
SAxx-EXECUTE
SAxx-CANCEL
SAxx-BLK_OPEN
SAxx-BLK_CLOS
SAxx-INT_LOCK
SAxx-SY_RUN
ABB Network Partner AB
DESCRIPTION:
Input for external position check function,
i.e. valid position of the apparatus
Input for open position indication in phase
L1
Input for open position indication in phase
L2
Input for open position indication in phase
L3
Input for close position indication in phase
L1
Input for close position indication in phase
L2
Input for close position indication in phase
L3
Blocking of updating of the position indica-
tion (pulse input from COMCON)
Resuming of updating of the position indica-
tion (pulse input from COMCON)
Input for manual setting of open position
(pulse input from COMCON)
Input for manual setting of close position
(pulse input from COMCON)
Input for blocking of updating (from BLK-
CONK at blocking of all apparatuses in a
bay)
Selection input (from BAYCON, signal
SELx)
Feedback selection input
Open direction for operation (pulse input
from COMCON)
Close direction for operation (pulse input
from COMCON)
Automatic operation permitted (signal from
BAYCON)
Execution of operation (pulse input from
COMCON)
Cancelling of the selected operation (pulse
input from COMCON)
Blocking input for open direction
Blocking input for close direction
Operation blocked by conditions from the
interlocking module
To be set to true when the synchro-check is
running