ABB REC 561 User Manual page 333

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 150-XEN
Page
6 - 48
Apparatus control
lowing figures show examples of different configurations. The terminal
diagram for the binary output module shows detailed information about
the terminal numbering.
Application software
To BLKCONL
CLOSE
&
From
SWI-
CON
OPEN
&
Fig. 36
Single pole command outputs with supervision
Fig. 36 and Fig. 37 are the standard configurations during operation of
high-voltage apparatuses. The double pole command is normally used to
avoid an unwanted operation of the apparatuses, due to an earth fault in
the switchyard. The output module is very flexible. So users can mostly
find solutions for their own requirements.
Application software
To BLKCONL
CLOSE
&
From
SWI-
CON
OPEN
&
Fig. 37
Double pole command outputs with supervision
ABB Network Partner AB
I/O-module
ERROR
BO1
BO2
BO3
BO4
.
.
.
BO24
I/O-module
ERROR
BO1
BO2
BO3
BO4
.
.
.
BO24
Version 1.0-00
Switchyard
Binary
Output
Module
Close
XA
coil
1
BO.01
2
BO.02
3
+
Open
coil
4
BO.03
5
BO.04
6
+
(X80150-36)
Switchyard
Binary
Output
Module
Close
coil
XA
1
4
BO.01
BO.03
2
+
5
-
BO.04
BO.02
6
3
Open
(X80150-37)
coil
-
-

Hide quick links: