ABB REC 561 User Manual page 363

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 150-XEN
Page
6 - 78
Apparatus control
Table 9: Input signals for BAYCONE
IN:
BExx-SEL_FDB6
BExx-SEL_FDB7
BExx-SEL_FDB8
Table 10: Output signals for BAYCONE
OUT:
BExx-REMOTE
BExx-STATION
BExx-LOCAL
BExx-SEL1
BExx-SEL2
BExx-SEL3
BExx-SEL4
BExx-SEL5
BExx-SEL6
BExx-SEL7
BExx-SEL8
BExx-RE
BExx-RE_BAYS
BExx-ACK_T_B
BExx-FDB_SEL1
BExx-FDB_SEL2
BExx-FDB_SEL3
BExx-FDB_SEL4
BExx-FDB_SEL5
ABB Network Partner AB
DESCRIPTION:
Input for individual selection relay energiz-
ing of apparatus 6
Input for individual selection relay energiz-
ing of apparatus 7
Input for individual selection relay energiz-
ing of apparatus 8
DESCRIPTION:
Indication of Remote operator place
Indication of Station operator place
Indication of Local operator place
Apparatus 1 is selected after reservation
acknowledgement from other bays
Apparatus 2 is selected after reservation
acknowledgement from other bays
Apparatus 3 is selected after reservation
acknowledgement from other bays
Apparatus 4 is selected after reservation
acknowledgement from other bays
Apparatus 5 is selected after reservation
acknowledgement from other bays
Apparatus 6 is selected after reservation
acknowledgement from other bays
Apparatus 7 is selected after reservation
acknowledgement from other bays
Apparatus 8 is selected after reservation
acknowledgement from other bays
A reservation has been made in this bay
Request for reservation of other bays
Acknowledgement to other bays that this
bay is reserved
Correct selection relay is energized for
apparatus 1
Correct selection relay is energized for
apparatus 2
Correct selection relay is energized for
apparatus 3
Correct selection relay is energized for
apparatus 4
Correct selection relay is energized for
apparatus 5
Version 1.0-00