ABB REC 561 User Manual page 490

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
Interlocking
Table 19: Input signals for BH_LINE_A
IN:
ILxx-Q6EX1
ILxx-Q6EX2
ILxx-Q1EX1
ILxx-Q1EX2
ILxx-Q9EX1
ILxx-Q9EX2
ILxx-Q9EX3
ILxx-Q9EX4
ILxx-Q9EX5
ILxx-Q9EX6
ILxx-Q9EX7
Table 20: Output signals for BH_LINE_A
OUT:
ILxx-Q0CLREL
ILxx-Q0CLITL
ILxx-Q6REL
ILxx-Q6ITL
ILxx-Q1REL
ILxx-Q1ITL
ILxx-Q51REL
ILxx-Q51ITL
ILxx-Q52REL
ILxx-Q52ITL
ILxx-Q53REL
ILxx-Q53ITL
ILxx-Q9REL
ILxx-Q9ITL
ILxx-Q8REL
ILxx-Q8ITL
1MRK 580 151-XEN
DESCRIPTION:
Input for an external condition for apparatus
Q6
Input for an external condition for apparatus
Q6
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
DESCRIPTION:
Closing of Q0 is allowed
Closing of Q0 is forbidden
Switching of Q6 is allowed
Switching of Q6 is forbidden
Switching of Q1 is allowed
Switching of Q1 is forbidden
Switching of Q51 is allowed
Switching of Q51 is forbidden
Switching of Q52 is allowed
Switching of Q52 is forbidden
Switching of Q53 is allowed
Switching of Q53 is forbidden
Switching of Q9 is allowed
Switching of Q9 is forbidden
Switching of Q8 is allowed
Switching of Q8 is forbidden
Page
6 - 205

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents