1 Application

I/O system configuration
Basic
This document describes the I/O system configuration that is used to add,
remove, or move I/O modules in the REC 561 and REL 531 terminal
Available I/O modules are:
products.
• BIM, Binary Input Module with 16 binary input channels
• BOM, Binary Output Module with 24 binary output channels
• IOM, Input/Output Module with 8 binary input and 12 binary output
channels
• MIM, mA Input Module with 6 analogue input channels
A product houses a maximum of 13 modules. REC 561 can have up
to 13 modules. REL 531 can have up to 5 modules and no MIM.
To configure, connect the function blocks that represent each I/O module
(BIM, BOM, IOM, and MIM) to a function block for the I/O positions
(IOP).