ABB REC 561 User Manual page 577

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 133-XEN
Page
7 - 58
1.1 Settings during normal
conditions
Table 1: How the settings affect different functions in the Disturbance Report
MMI
Function
Setting
menu
Operation
Operation (On/Off) Yes
Recording
Recording times
times
(tPre, tPost, tLim)
Binary sig-
Trig operation and
nals
trig level
Indication mask (for
automatic scrolling)
Analogue
Operation (On/Off) No
signals
Trig over/under
function
Fault Loca-
Fault locator set-
tor
tings (tFilter, Dis-
tance Unit)
2 Operation
Disturbance report - Settings
Disturbance
Disturbance
Summary
Recorder
(scrolled on
MMI)
Yes
No
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
No
No
MMI submenu:
Settings
DisturbReport
Operation
Operation can be set to On or Off. If Off is selected, note that no Distur-
bance Report is registered, including Indications, Fault locator, Event
Recorder, and Disturbance Recorder.
Operation = Off:
• Disturbances are not stored.
• LED information (yellow - start, red - trip) is not stored or changed.
• No Disturbance Summary is scrolled on the built-in MMI.
Operation = On:
• Disturbances are stored, disturbance data can be read from the built-
in MMI and from a front-connected PC or Station Monitoring Sys-
tem (SMS).
• LED information (yellow - start, red - trip) is stored.
• The Disturbance Summary is automatically scrolled on the built-in
MMI for the two latest registered disturbances, until cleared.
ABB Network Partner AB
Indications
Event list
(SMS)
Yes
Yes
No
Yes
Yes
Yes
No
No
No
No
Yes
Yes
No
No
Version 1.0-00
Trip
Fault
values
locator
Yes
Yes
No
No
Yes
Yes
No
No
No
No
Yes
Yes
No
Yes