4.2.9 Autoreclosing

Apparatus control
COMCON
CLOSE
EXECUTE
SWICONB
CLOSE
EXECUTE
SEL_CLOS
EXE_CLOS
SY_RUN
SY_FAIL
Timer
&
INPUT
Fig. 31
Connections between external synchronising equipment and
the apparatus control modules, alternative 3
In Fig. 28 to Fig. 31, the SY_FAIL input supervises the synchronisation
time. If the relay does not reach synchronism within a certain time,
SY_FAIL is activated and resets the complete operation sequence.
Fig. 32 shows the interaction between the autoreclosing (AR) module and
the apparatus control modules. The OR gate for the close signal must have
the same execution cyclicity as the autoreclosing module. The signal
BLK_AR from SWICON is used to block the autoreclose function at the
moment the circuit breaker is under operation.
Circuit Breaker
SWICONA(B)
SEL_CLOS
EXE_CLOS
(AR_SEL)
BLK_AR
INHIBIT
Fig. 32
Connections between autoreclosing (AR) module and appara-
tus control modules
BI/BO
External synchronising equipment
SYNCH
START
&
IN
PROGRESS
≥1
ON
≥1
&
AR
CLOSECB
1MRK 580 150-XEN
Page
6 - 45
CB
close
coil
CLOSE
+
FAULT
(X80150-31)
CLOSE
To output board