ABB REC 561 User Manual page 380

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
Apparatus control
Table 20: Output signals for SWICONC
OUT:
SCxx-CX
SCxx-POS_ERR
SCxx-MA_UPD_P
SCxx-SEL_OPEN
SCxx-SEL_CLOS
SCxx-EXE_OPEN
SCxx-EXE_CLOS
SCxx-SEL_RES
SCxx-SEL_ERR
SCxx-CMD_ERR
SCxx-AU_OP_P
1MRK 580 150-XEN
DESCRIPTION:
Indication that the apparatus is in close
position. Result of the input indication or
blocking of the process updating or by the
manually entered close position
Position error, i.e. the position indication is
both open and closed or is in middle posi-
tion longer than T_POSERR or the input
POSIND_V is false
Output indicating manual control of position
updating
Selection output for open direction
Selection output for close direction
Execute output for open direction (settable
pulse length)
Execute output for close direction (settable
pulse length)
Reset the selection after successful or failed
operation (pulse output)
Output indicating a failure in the selection, if
no feedback select signal FDB_SEL is acti-
vated before the time T_SEL has elapsed
Output indicating a command error. That is
done if the position indication of the exe-
cuted apparatus does not indicate a start in
the position change before the time
T_START has elapsed
Automatic operation is permitted, i.e. the
operator place selector is not in Local posi-
tion, the apparatus is not reserved, not man-
ual selected or not blocked (neither
operation nor update of position). The inter-
locking conditions are not considered
Page