ABB REC 561 User Manual page 404

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
4.2.2.2 Signals from bus
coupler
Interlocking
EXDUP_BS
Signal if there is no transmission error from the bay that contains the
above information. This signal is taken from the data valid output on the
command function block.
For a bus-coupler bay in section 1, these conditions are valid:
BBTR_OP (sect.1)
DCOPTR (A1A2)
DCOPTR (B1B2)
BBTR_OP (sect.2)
VP_BBTR (sect.1)
VPDCTR (A1A2)
VPDCTR (B1B2)
VP_BBTR (sect.2)
EXDUP_AB (sect.1)
EXDUP_DC (A1A2)
EXDUP_DC (B1B2)
EXDUP_AB (sect.2)
Fig. 16
Signals to a bus-coupler bay in section 1 from any bays in each
section
For a bus-coupler bay in section 2, the same conditions as above are valid
by changing section 1 to section 2 and vice versa.
If the busbar is divided by bus-section disconnectors into bus sections, the
signals BC_AB from the busbar coupler of the other busbar section must
be transmitted to the own busbar coupler if both disconnectors are closed.
Section 1
A1
B1
C
Fig. 17
Busbars divided by bus-section disconnectors (circuit break-
ers)
&
≥1
&
&
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
ABC_BC
1MRK 580 151-XEN
Page
6 - 119
BBTR_OP
VP_BBTR
EXDUP_AB
(X80151-16)
A2
B2
C
(X80151-17)