ABB REC 561 User Manual page 487

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 151-XEN
Page
6 - 202
6.2.9 DB_BUS_B
Interlocking
Table 15: Input signals for DB_LINE
IN:
IAxx-Q9EX4
IAxx-Q9EX5
Table 16: Output signals for DB_LINE
OUT:
IAxx-Q9REL
IAxx-Q9ITL
IAxx-Q53REL
IAxx-Q53ITL
IAxx-Q8REL
IAxx-Q8ITL
Table 17: Input signals for DB_BUS_B
IN:
ICxx-Q02_OP
ICxx-Q02_CL
ICxx-Q62_OP
ICxx-Q62_CL
ICxx-Q2_OP
ICxx-Q2_CL
ICxx-Q54_OP
ICxx-Q54_CL
ICxx-Q55_OP
ICxx-Q55_CL
ICxx-Q53_OP
ICxx-Q53_CL
ICxx-Q25_OP
ICxx-Q25_CL
ICxx-EXDUP_ES
ICxx-EXVVA_ES
ICxx-Q62EX1
ABB Network Partner AB
DESCRIPTION:
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
DESCRIPTION:
Switching of Q9 is allowed
Switching of Q9 is forbidden
Switching of Q53 is allowed
Switching of Q53 is forbidden
Switching of Q8 is allowed
Switching of Q8 is forbidden
DESCRIPTION:
Signal is 1 if Q02 is open
Signal is 1 if Q02 is closed
Signal is 1 if Q62 is open
Signal is 1 if Q62 is closed
Signal is 1 if Q2 is open
Signal is 1 if Q2 is closed
Signal is 1 if Q54 is open
Signal is 1 if Q54 is closed
Signal is 1 if Q55 is open
Signal is 1 if Q55 is closed
Signal is 1 if Q53 is open
Signal is 1 if Q53 is closed
Signal is 1 if Q25 on busbar B is open
Signal is 1 if Q25 on busbar B is closed
Signal is 1 if there is no transmission error
from any bay containing earthing switches
Q25
Signal is 1 if the interlocking programs in all
bays containing earthing switches Q25 are
running
Input for an external condition for apparatus
Q62
Version 1.0-00

Hide quick links: