Signal List - ABB REC 561 User Manual

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 170-XEN
Page
5 - 80

6.2 Signal list

Auto-reclosing - Single- and/or
three-phase
Signal list indicating the input and output signals which can be interfaced
with the auto-recloser 1. Data is same for other auto-recloser functions (2
to 6) with signal prefix AR02- to AR06-.
IN:
AR01-TRSOTF
AR01-TPTRIP
AR01-START
AR01-ON
AR01-OFF
AR01-CBREADY
AR01-CBCLOSED
AR01-INHIBIT
AR01-PLCLOST
AR01-WAIT
AR01-SYNC
OUT:
AR01-CLOSECB
AR01-SETON
AR01-INPROGR
AR01-WFMASTER
AR01-P1PH
AR01-P3PH
AR01-READY
AR01-SP1
AR01-TP1
AR01-TP2
AR01-TP3
AR01-TP4
AR01-UNSUC
ABB Network Partner AB
DESCRIPTION:
Trip from switch-onto-fault
Three phase trip
Protection function trip to AR
Enable auto-recloser
Disable auto-recloser
CB Ready for operation
CB closed
Inhibit auto-recloser
Permissive communication channel out of
service
Wait from master for sequential reclosing
Permission from synchro-check/energizing
check function
DESCRIPTION:
Closing command to breaker
Auto-recloser set on
Auto-reclose operation in progress
Wait from master for sequential reclosing
Permit 1 phase tripping
Prepare for 3 phase trip
Auto-reclose ready for new operation
1 phase reclosing in progress
3 phase, shot 1 in progress
3 phase, shot 2 in progress
3 phase, shot 3 in progress
3 phase, shot 4 in progress
Auto-reclose unsuccessful
Version 1.0-00