Appendix; Terminal Diagram; Signal List - ABB REC 561 User Manual

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00

6 Appendix

6.1 Terminal diagram

6.2 Signal list

Pulse counter
PCxx
BLOCK
TMIT_VAL
BIM_CONN
NAME
Fig. 2
Simplified terminal diagram of the Pulse Counter function
Table 1: Input and output signals for Pulse Counter No. xx
IN:
PCxx-BLOCK
PCxx-TMIT_VAL
PCxx-BIM_CONN
OUT:
PCxx-INVALID
PCxx-RESTART
PCxx-BLOCKED
PCxx-NEW_VAL
1MRK 580 187-XEN
PulseCounter
INVALID
RESTART
BLOCKED
NEW_VAL
DESCRIPTION:
Input to block the counter
Pulse input to perform an additional reading
of the counter value. The reading is per-
formed on the positive flank of the pulse
Input to be connected to the used input of
the function block for the Binary input mod-
ule (BIM)
DESCRIPTION:
The output is set if the Binary input module
(BIM), where the pulse input is located, fails
or has wrong configuration
The output is set when the reported value
does not comprise a complete integration
cycle.
The output is set when the BLOCK input is
set or the Binary input module (BIM), where
the pulse input is located, is inoperative.
The output is set if the counter value was
updated since the last report (pulse output)
Page
7 - 37
(X80187-2)