Settings During Test; Test Mode; Activation Of Manual Triggering - ABB REC 561 User Manual

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00

3 Settings during test

3.1 Test mode

3.2 Activation of manual
triggering
Disturbance report - Settings
During testing, the operation of the Disturbance Report is required. The
setting of this operation is found at the MMI submenu:
Test
Test Mode
DisturbReport
Operation, DisturbSummary
When TestMode is set to On (Test/Mode/Operation = On), the setting of
the Disturbance Report parameters have the following impact:
Operation = Off
DisturbSummary = Off
• Disturbances are not stored.
• LED information is not shown on the MMI and not stored.
• No Disturbance Summary is scrolled on the MMI.
Operation = Off
DisturbSummary = On
• Disturbances are not stored.
• LED information (yellow - start, red - trip) are shown on the built-in
MMI, but not stored in the terminal.
• Disturbance summary is automatically scrolled on the built-in MMI
for the two latest registered disturbances, until cleared. The informa-
tion is not stored in the terminal.
Operation = On
DisturbSummary = Off or On
• The Disturbance Report works as in normal mode.
• Disturbances are stored. Data can be read from the built-in MMI, a
front-connected PC, or SMS.
• LED information (yellow - start, red - trip) is stored.
• Disturbance Summary is automatically scrolled on the built-in MMI
for the two latest registered disturbances, until cleared.
• All disturbance data stored during test mode remains in the terminal
when returning to normal mode.
A Disturbance Report can be manually triggered from the built-in MMI, a
front-connected PC, or SMS. When the trig is activated, the manual trig
signal is generated. This feature is especially useful for testing.
1MRK 580 133-XEN