8.3 Setting table

Table 3:
PARAMETER:
SETTING RANGE:
Name
13 character string
Operation
Off, On
Calib
Off, On
ChSign
Off, On
Unit
5 character string
Hysteres
(0.0-20.0)mA
AlRemove
Off, On
I_Max
(-20.00 - 20.00)mA
SampRate
(5 - 255)Hz
EnAlarm
Off, On
MinValue
(-1000.00- 1000.00)(a)
HiAlarm
(-20.00 - 20.00)mA
HiWarn
(-20.00 - 20.00)mA
LowWarn
(-20.00 - 20.00)mA
LowAlarm
(-20.00 - 20.00)mA
RepInt
(0-3600)Seconds
EnDeadB
Off, On
DeadBand
(0.00-20.00)mA
EnIDeadB
Off, On
IDeadB
(0.00-1000.00)mA
EnDeadBP
Off, On
Direct current measuring unit
DESCRIPTION:
Up to 13 characters long name for the measuring channel
Operation of the measuring channel enabled (On) or disabled (Off)
Activation (On) or deactivation (Off) of a production calibration. In a
moment only possible to read. The production calibration is always
On.
Changes the polarity of connected input current (On)
Up to 5 characters long name for the unit of the measuring con-
verter input measuring quantity
Hysteresis for the set values of the monitoring measuring elements
in one measuring channel.
When On produces an immediate event when any of alarm moni-
toring measuring elements resets.
Determines the maximum permitted input current to the measuring
channel
Sampling frequency for the measuring channel
When On produces an immediate event at operation of any alarm
monitoring measuring elements
Determines the minimum value of the measuring transducer pri-
mary measuring quantity, which corresponds to the minimum per-
mitted input current I_Min
Determines the operating value of the monitoring measuring ele-
ment, which produces logical signal MInm-HIALARM (n = 1...6 and
m = 1...6)
Determines the operating value of the monitoring measuring ele-
ment, which produces logical signal MInm-HIWARN (n = 1...6 and
m = 1...6)
Determines the operating value of the monitoring measuring ele-
ment, which produces logical signal MInm-LOWWARN (n = 1...6
and m = 1...6)
Determines the operating value of the monitoring measuring ele-
ment, which produces logical signal MInm-LOWALARM (n = 1...6
and m = 1...6)
Duration of time interval between two reports at periodic reporting
function. Setting equal to 0 disables the periodical reporting
Enables (On) or disables (Off) the amplitude dead band supervision
function
Width of the amplitude dead band within the ADBS function
Enables (On) or disables (Off) the integrating dead band supervi-
sion function
Determines the width of the current band within the IDBS function.
Be aware of the sampling frequency.
Enables (On) or disables (Off) the periodic dead band reporting
1MRK 580 154-XEN
Page
7 - 15