4 Configurations
4.1 General
4.2 Project-specific logic
4.2.1 Single breaker
arrangement, line
bay
4.2.1.1 Signals from bypass
busbar
Interlocking
This section describes how the interlocking for a certain switchgear con-
figuration can be realized by using standard interlocking modules and
their interconnections. It also describes the parameter settings. The
EXVVA_xx input signals, which are normally not used, are always set to
1=FIXD-ON. The inputs for delivery specific conditions (QxEXy) are set
to 1=FIXD-ON, if they are not used except:
• Q9EX2 and Q9EX4 in modules BH_LINE_A and BH_LINE_B
• Q0EX3 in module AB_TRAFO
which are set to 0=FIXD-OFF.
The signals from other bays connected to the module ABC_LINE are
described below.
To derive the signals:
C_DC_OP
All line disconnectors on bypass C except in the own bay are open.
VP_C_DC
The switch status of C_DC is valid.
EXDU_BPB
Signal if no transmission error from any bay connected to a bypass bus-
bar.
These signals from each line bay (ABC_LINE) except that of the own bay
are needed:
Q7OPTR
Q7 is open
VPQ7TR
The switch status Q7 is valid.
EXDU_BPB
Signal if there is no transmission error from the bay that contains the
above information. This signal is taken from the data valid output on the
command function block.
1MRK 580 151-XEN
Page
6 - 111