PARAMETER:
SETTING RANGE: DESCRIPTION:
HiWarn
(0-99999)A
HiAlarm
(0-99999)A
EnDeadB
Off, On
DeadBand
(0-99999)A
EnIDeadB
Off, On
IDeadB
(0-99999)A
EnDeadBP
Off, On
Operation
Off, On
RepInt
(0-3600)Seconds
EnAlarms
Off, On
EnAlRem
Off, On
Hysteres
(0.0-1999.9)kV
LowAlarm
(0.0-1999.9)kV
LowWarn
(0.0-1999.9)kV
HiWarn
(0.0-1999.9)kV
HiAlarm
(0.0-1999.9)kV
EnDeadB
Off, On
DeadBand
(0.0-1999.9)kV
EnIDeadB
Off, On
IDeadB
(0.0-1999.9)kV
EnDeadBP
Off, On
Measurement of alternating
quantities
Determines the operating value of the monitoring element which pro-
duces logical signal DA0n-HIWARN (n=6..10)
Determines the operating value of the monitoring element which pro-
duces logical signal DA0n-HIALARM (n=6..10)
Enables (On) or disables (Off) the amplitude dead-band supervision
function
Width of the amplitude dead-band within the ADBS function
Enables (On) or disables (Off) the integrating dead-band supervision
function.
Determines the width of the band within the IDBS function. Be aware of
the sampling frequency
Enables (On) or disables (Off) the periodic dead-band reporting
Mean voltage measuring channel
Operation of the measuring channel enabled (On) or disabled (Off)
Duration of time interval between two reports at periodic reporting
function. Setting to 0 disables the periodic reporting.
Produces an immediate event at operation of any alarm monitoring ele-
ment, when On
Produces an immediate event at reset of any alarm monitoring element,
when On.
Hysteresis for the set values of the monitoring elements in one measur-
ing channel.
Determines the operating value of the monitoring element which pro-
duces logical signal DA11-LOWALARM
Determines the operating value of the monitoring element which pro-
duces logical signal DA11-LOWARN
Determines the operating value of the monitoring element which pro-
duces logical signal DA11-HIWARN
Determines the operating value of the monitoring element which pro-
duces logical signal DA11-HIALARM
Enables (On) or disables (Off) the amplitude dead-band supervision
function
Width of the amplitude dead-band within the ADBS function
Enables (On) or disables (Off) the integrating dead-band supervision
function.
Determines the width of the band within the IDBS function. Be aware of
the sampling frequency
Enables (On) or disables (Off) the periodic dead-band reporting