ABB REC 561 User Manual page 383

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 150-XEN
Page
6 - 98
7.3 Setting table
7.3.1 BAYCONx
Table 23: Setting table for BAYCONx
PARAMETER: SETTING RANGE: DESCRIPTION:
T_CAN_RE
7.3.2 COMCON
Table 24: Setting table for COMCON
PARAMETER: SETTING RANGE: DESCRIPTION:
T_LO_OP
T_RES
7.3.3 SWICONA
Table 25: Setting table for SWICONA
PARAMETER:
T_POSERR
T_POL
T_SEL
T_START
T_PULSE
Apparatus control
0.0-200.0 s
Timeout when the reset of the reservation
acknowledgement is not done by the
requesting bays, for example, because of
communication error. To be set from CAP
531
0.0-200.0 s
Maximum time between a select and the
execute command coming from the opera-
tor. Also the maximum time between the
request to override and the following select.
To be set from CAP 531
0.0-200.0 s
Allowed time (for BAYCON) to make the
reservation. To be set from CAP 531
SETTING
DESCRIPTION:
RANGE:
0.0-200.0 s
Allowed time for middle position. To be set
from CAP 531
0.0-200.0 s
Time parameter for pole discordance.
Allowed time to have discrepancy between
the poles. To be set from CAP 531
0.0-200.0 s
Allowed time from selection to feedback
select. To be set from CAP 531
0.0-200.0 s
Allowed time from execute to position indi-
cation change. To be set from CAP 531
0.0-200.0 s
Time parameter for command output pulse
length. T_PULSE = 0 gives a steady com-
mand output signal. To be set from CAP
531