7 Speed Connection

Function
ANA CMD Select
Speed 1
Preset
Speed 2
Preset
Speed 3
Preset
Speed 4
Preset
Speed 5
Preset
Speed 6
Preset
Speed 7
Preset
J4-11
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED starts Forward motor rotation.
J4-12
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED starts Reverse motor rotation.
J4-13
OPEN selects setting of "ANA CMD Select" parameter.
CLOSED selects Analog Input #1.
J4-14
Selects preset speeds as defined in Table 3-8.
J4-15
Selects preset speeds as defined in Table 3-8.
J4-16
Selects preset speeds as defined in Table 3-8.
J4-17
If J4-17 is connected, you must set Level 2 Protection block, External Trip to
"ON" to activate the opto input.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
CLOSED allows normal operation.
3-18 Receiving and Installation
Figure 3-12 7 Speed Connection Diagram
Table 3-8
Speed Select 1
Open
Closed
Closed
Closed
Closed
Open
Open
Open
Speed Select 2
Open
Open
Closed
Closed
Open
Open
Closed
Closed
Speed Select 3
Open
Open
Open
Closed
Closed
Closed
Closed
Open