FAULT MESSAGE
Invalid Base ID
Commun Timeout
2 SEC Overload
1 MIN Overload
CUR LIM Timeout
HW Surge Current
Heat Sink Temp
Hardware Protect
Regen RES Power
Precharge FLT
Bus Overvoltage
Bus Undervoltage
Software VER FLT
External Trip
FE EEPROM Error
New Base ID
*
Note: An overload fault cannot be reset (cleared) until the "% OVERLOAD LEFT"
counter reaches 100%.
MN715J
Table 5-1 Fault Messages
Failure to determine control horsepower and input voltage configuration from
the Power Base ID value in software.
Communication failure between interface board and motor control.
*
Output current exceeded 3 second rating.
*
Output current exceeded 1 minute rating.
Peak output current exceeded PK CURRENT LIMIT parameter value.
High output current condition detected (greater than 250% of rated output
current).
Control heatsink exceeded upper temperature limit.
A general hardware fault was detected but cannot be isolated. Ground Fault
detected (output current leakage to ground) or power supply undervoltage.
Regen power exceeded dynamic brake resistor rating.
DC Bus charging error detected.
High DC Bus voltage.
Low DC Bus voltage.
Keypad and control software versions are incompatible.
Connection between J4-17 and J4-18 is open.
Non-volatile memory on the keypad has failed.
Control board detected a change in the Power Base ID value in software.
DESCRIPTION
Troubleshooting 5-5