EPOT 2 Wire Connection

Figure 3-18 Electronic POT 2 Wire Connection Diagram
J4-11
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED to enable operation in the Forward direction.
J4-12
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED to enable operation in the Reverse direction.
J4-13
OPEN for normal speed mode. Terminal strip speed source is selected in the
Level 1 Input block, ANA CMD Select parameter.
CLOSED to enable the Electronic Potentiometer Mode.
J4-14
OPEN selects ACC / DEC / S-CURVE group 1.
CLOSED selects group 2.
J4-15
Momentary CLOSED increases motor speed while closed.
J4-16
Momentary CLOSED decreases motor speed while closed.
J4-17
If J4-17 is connected, you must set Level 2 Protection block, External Trip to
"ON" to activate the opto input.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
CLOSED allows normal operation.
3-24 Receiving and Installation