Process Control Connection

Figure 3-15 Process Control Connection Diagram
J4-11
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED starts Forward motor rotation.
J4-12
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED starts Reverse motor rotation.
Note: Simultaneous closure of J4-11 and J4-12 will cause the motor to regen to stop
(not coast).
J4-13
OPEN selects the input specified in the Level 1 Input block,
ANA CMD Select parameter.
CLOSED selects the closed loop feature of the Process Control mode.
Note: The process will run in one direction. For example, if the forward line (J4-11)
is closed, the process will only run in the forward direction. The PID algorithm
will not reverse the direction automatically.
J4-14
OPEN allows normal operation.
CLOSED jogs the motor in the forward direction.
J4-15
OPEN allows normal operation.
CLOSED jogs the motor in the reverse direction.
Note: Simultaneous closure of J4-14 and J4-15 selects jog forward.
J4-16
OPEN allows normal operation.
CLOSED to reset a fault condition.
J4-17
If J4-17 is connected, you must set Level 2 Protection block, External Trip to
"ON" to activate the opto input.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
CLOSED allows normal operation.
MN715J
Receiving and Installation 3-21