115VAC 1 Phase Wire Size and Protection Devices
Table 3-6 Wire Size and Protection Devices - 1 phase
Control Output
Control Output
Rating HP
0.33
0.5
0.75
1.0
Note: All wire sizes are based on 75°C copper wire, 1% line impedance. Higher
temperature, smaller gauge wire may be used per NEC and local codes.
Recommended fuses are based on 40°C ambient, maximum continuous
control output current and no harmonic current.
Figure 3-5 Single Phase AC Power and Motor Connections
*
*
3-10 Receiving and Installation
Fast Acting
Amps
10
10
15
20
Baldor Series 15J Control
Input Fuse
Input Fuse
Time Delay
Amps
10
10
10
15
Wire Gauge
Wire Gauge
AWG
mm
2
14
2.08
14
2.08
14
2.08
14
2.08
MN715J