Controlling the Web-IO with TCP/UDP Sockets
Input Trigger
Here you specify which inputs are to be monitored for which
state. If you are activating multiple inputs in an alarm for
monitoring, there is an AND-operation on the conditions.
Example:
In Alarm 1 Input 1 was activated for ON, Input 2 for OFF.
An alarm is only sent to the TCP application if both conditions
are met. In this case: Input 1= ON, Input 2 = OFF.
Interval
To send alarms over an existing TCP connection it is practical
to set the E parameter here so that only one alarm message is
sent when the alarm condition occurs.