W&T 57630 Manual page 209

Web-io series 12+12 digital
Table of Contents

Advertisement

W&T
Error message
UDP port number invalid: use Port 42279
Checksum error: factory defaults were loaded
SNMP: IP address or name of Snmp manager not
entered
UDP alarm: IP address or name of UDP server not
entered
UDP alarm: Port of UDP server not entered
Number of pulses exceeds 2000/sec: pulse mode input
x stopped!
50xxx-Mode: Invalid UPD IP address
50xxx-Mode: Invalid TCP IP address
Watchdog timer expired
Box2Box: Invalid port number
Box2Box: Invalid slave IP address
Port number assigned more than once
50xxx: Invalid local port number
Box2Box: Invalid local port number
Box2Box: Slave access denied, please check Box2Box
settings
Box2Box: Slave is in Box2Box Master Mode
Box2Box: Master could not be cleared, please log out
Overload: Details under Diag>>Test>OutputConfig
Restart using Delete report
Subject to errors and modifications:
Error messages
Possible cause
Duplicate assigned port number, port number greater than
65535 or text given instead of digits for port number
ROM error detected in configuration area
see Config >> Device >> Alarm >> Alarmx >> SNMP
see Config >> Device >> Alarm >> Alarmx >> UDP
see Config >> Device >> Alarm >> Alarmx >> UDP
Input signal frequency too high
see Config >> Device >> Mode 50xxx >> UDP Client
see Config >> Device >> Mode 50xxx >> TCP Client
Safety watchdog detected no network traffic within the
specified timeout time and the outputs were set to Safety
State
Port number greater than 65535 or text entered instead of
digits for port number. Config >> Device >> Box 2 Box
No IP address specified or invalid address format. Config
>> Device >> Box 2 Box
Each mode must use a unique port number (see Appendix
7 Port Number List)
Duplicate assigned port number, port number greater than
65535 or text entered instead of digits for port number.
Config >> Device >> Mode 50xxx
Duplicate assigned port number, port number greater than
65535 or text entered instead of digits for port number.
Config >> Device >> Mode Box2Box
Slave many be in Operator or Administrator Login, slave
working in 50xxx mode or is blocked by another mode.
see Config >> Device >> Box 2 Box for Slave Web-IO
Slave is in Operator or Administrator Login and could not
clear the master connection data
An overload or no load was detected on one or more
outputs
After a load error the corresponding output is enabled
again using Delete report.
After an error caused by high-frequency input signals,
pulse mode is activated again after Delete report.