ACS 400 Basic Parameters

The ACS 400 has a large number of parameters. Of these, only the basic parameters are initially
visible.
Setting up only a few basic parameters is sufficient for applications where the preprogrammed
application macros of the ACS 400 can provide all desired functionality. For a full description of
programmable features provided by the ACS 400, see "ACS 400 Complete Parameter List", starting
on page 51.
The following table lists the basic parameters.
S = Parameters can be modified only when the drive is stopped.
Code Name
Group 99
START-UP DATA
9901 LANGUAGE
Language selection.
0 =
(
ENGLISH
UK
1=
(
)
ENGLISH
US
2 =
GERMAN
3 =
ITALIAN
9902 APPLIC MACRO
Selects application macro.Sets parameter values to their default values. Refer to
"Application Macros", starting on page 41 for detailed description of each macro.
0 =
FACTORY
1=
ABB STANDARD
2 = 3-
WIRE
3 =
ALTERNATE
4 =
MOTOR POT
5 =
/
HAND
AUTO
6 =
PID CONTROL
7 =
PREMAGN
Default value: 0 (
9905 MOTOR NOM VOLT
Nominal motor voltage from motor nameplate. Range of this parameter depends on the
type of the ACS 400.
Default value for 400 V unit: 400 or 480 V depending on application macro selected.
Default value for 200 V unit: 200 or 240 V depending on application macro selected.
9906 MOTOR NOM CURR
Nominal motor current from motor nameplate. Values for this parameter range from 0.5*
I
- 1.5* I
, where I
N
N
Default value: I
N
9907 MOTOR NOM FREQ
Nominal motor frequency from motor nameplate.
Range: 0 - 250 Hz
Default: 50 Hz or 60 Hz depending on macro selected.
ACS 400 User's Guide
)
4 =
SPANISH
5 =
PORTUGUESE
6 =
DUTCH
7 =
FRENCH
)
FACTORY MACRO
is nominal current of the ACS 400.
N
8 =
12 = (reserved)
DANISH
9 =
FINNISH
10 =
SWEDISH
11 =
RUSSIAN
User
S
á
á
á
á
37