Application Macro Factory (1)
This macro is intended for applications where there is no control panel available. It provides a
general purpose I/O configuration that is typically used in North America.
Note! The value of parameter 9902 is 0 (
mA
Input signals
• Start, stop and direction
(DI1,2,3)
• Analog reference (AI1)
• Ramp pair 1/2 selection (DI5)
*Note! DI 4 is used to configure ACS 400. It is read only once when power is connected. When
DI 4 is connected (1) the following applies:
•
All parameters marked * are determined by the DI4 input.
•
Motor nominal values are 480 V and 60 Hz and 1720 rpm.
•
Input and output signals are scaled according to 60 Hz.
•
Maximum frequency is 60 Hz.
Note! Remote stop signal must be present to activate start/stop in local mode.
Factory (1) parameter values:
*9905
MOTOR NOM VOLT
*9907
MOTOR NOM FREQ
*9908
MOTOR NOM SPEED
*1001
EXT
1002
2
EXT
1003
DIRECTION
1102
1/
EXT
1103
EXT REF
ACS 400 User's Manual
SCR
1
AI1
2
AGND
3
+10V
4
AI2
5
AGND
6
AO1
7
AGND
8
+24V
9
DCOM1
10
DI1
11
DI2
12
DI3
13
DI4
14
DI5
15
DCOM2
16
RO1C
17
RO1A
18
RO1B
19
RO2C
20
RO2A
21
RO2B
22
Output signals
480 V
60 Hz
1720 rpm
1
4 (
1
COMMANDS
DI
P
0 (
COMMANDS
NOT SEL
3 (
REQUEST
2
6 (
1)
EXT
SEL
EXT
1
1 (
1)
SELECT
AI
). DI 4 is connected.
FACTORY
External Reference 1: 0...10 V <=> 0...60 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...60 Hz
+24 VDC
Momentary activation with DI2 activated: Start
Momentary deactivation: Stop
Fwd/Rev: activate to reverse rotation direction
Must be connected!*
Ramp pair selection. Activate to select ramp pair 2.
Relay ouput 1, programmable
Default: Fault => 17 connected to 18
Relay ouput 2, programmable
Default: Running => 20 connected to 22
• An. output AO:
Frequency
• Relay output 1: Fault
• Relay output 2: Running
*1105
1
EXT REF
1106
2
EXT REF
SELECT
*1201
CONST SPEED SEL
,2
,
)
*1503
P
P
AO CONTENT MAX
)
1601
RUN ENABLE
)
1604
FAULT RESET SEL
*2008
MAXIMUM FREQ
2105
PREMAGN SEL
2201
/
1/2
ACC
DEC
V/I jumper S1
0 -10 V
AI1:
0 -10 V
AI2:
60 Hz
MAX
0 (
)
KEYPAD
0 (
NOT SEL
60 Hz
0 (
NOT SEL
6 (
/
START
STOP
60 Hz
0 (
NOT SEL
5 (
5)
SEL
DI
)
)
)
)
43