Application Macro Factory (1)

This macro is intended for applications where there is no control panel available. It provides a
general purpose I/O configuration that is typically used in North America.
Note! The value of parameter 9902 is 0 (
mA
Input signals
• Start, stop and direction
(DI1,2,3)
• Analog reference (AI1)
• Ramp pair 1/2 selection (DI5)
*Note! DI 4 is used to configure ACS 400. It is read only once when power is connected. When
DI 4 is connected (1) the following applies:
All parameters marked * are determined by the DI4 input.
Motor nominal values are 480 V and 60 Hz and 1720 rpm.
Input and output signals are scaled according to 60 Hz.
Maximum frequency is 60 Hz.
Note! Remote stop signal must be present to activate start/stop in local mode.
Factory (1) parameter values:
*9905
MOTOR NOM VOLT
*9907
MOTOR NOM FREQ
*9908
MOTOR NOM SPEED
*1001
EXT
1002
2
EXT
1003
DIRECTION
1102
1/
EXT
1103
EXT REF
ACS 400 User's Manual
SCR
1
AI1
2
AGND
3
+10V
4
AI2
5
AGND
6
AO1
7
AGND
8
+24V
9
DCOM1
10
DI1
11
DI2
12
DI3
13
DI4
14
DI5
15
DCOM2
16
RO1C
17
RO1A
18
RO1B
19
RO2C
20
RO2A
21
RO2B
22
Output signals
480 V
60 Hz
1720 rpm
1
4 (
1
COMMANDS
DI
P
0 (
COMMANDS
NOT SEL
3 (
REQUEST
2
6 (
1)
EXT
SEL
EXT
1
1 (
1)
SELECT
AI
). DI 4 is connected.
FACTORY
External Reference 1: 0...10 V <=> 0...60 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...60 Hz
+24 VDC
Momentary activation with DI2 activated: Start
Momentary deactivation: Stop
Fwd/Rev: activate to reverse rotation direction
Must be connected!*
Ramp pair selection. Activate to select ramp pair 2.
Relay ouput 1, programmable
Default: Fault => 17 connected to 18
Relay ouput 2, programmable
Default: Running => 20 connected to 22
• An. output AO:
Frequency
• Relay output 1: Fault
• Relay output 2: Running
*1105
1
EXT REF
1106
2
EXT REF
SELECT
*1201
CONST SPEED SEL
,2
,
)
*1503
P
P
AO CONTENT MAX
)
1601
RUN ENABLE
)
1604
FAULT RESET SEL
*2008
MAXIMUM FREQ
2105
PREMAGN SEL
2201
/
1/2
ACC
DEC
V/I jumper S1
0 -10 V
AI1:
0 -10 V
AI2:
60 Hz
MAX
0 (
)
KEYPAD
0 (
NOT SEL
60 Hz
0 (
NOT SEL
6 (
/
START
STOP
60 Hz
0 (
NOT SEL
5 (
5)
SEL
DI
)
)
)
)
43