Code Name
Group 13
ANALOG INPUTS
1301 MINIMUM AI1
Minimum value of AI1 in per cent. Defines relative analog input value where frequency
reference reaches minimum value.
Range: 0 - 100 %
Default value: 0 %
Group 15
ANALOG OUTPUT
1503 AO CONTENT MAX
Defines output frequency where analog output reaches 20 mA.
Default value: 50.0 Hz or 60.0 Hz depending on the application macro selected.
Note! Analog output content is programmable. Values given here are
valid only if other analog output configuration parameters have
not been modified. Description of all parameters is given in
"ACS 400 Complete Parameter List" starting on page 51.
Group 20
LIMITS
2003 MAX CURRENT
Maximum output current.
Range: 0.5* I
- 1.66* I
N
Default value: 1.5 * I
2008 MAXIMUM FREQ
Maximum output frequency.
Range: 0 - 250 Hz
Default value: 50 Hz or 60 Hz depending on the application macro selected.
ACS 400 User's Guide
, where I
is nominal current of the ACS 400.
N
N
N
User
The table continues on the next page.