Menu Functions

Scroll through the Parameter groups for the desired menu function. Press and hold ENTER until the
display blinks to start the function.
Note! The ACS100-PAN upload and download functions are not operational with ACS 400.
Relatively small permanent memory of the ACS100-PAN cannot store all the ACS 400
parameter values.
Select between basic and full menu
Visible if Full menu
is active

Resetting the Drive from the Control Panel

When the red LED of the ACS 400 is on or blinking, a fault is active.
To reset a fault when the red LED is on, press the START/STOP button.
Caution! This may start the drive, when in remote control.
To reset a fault when the red LED is blinking, turn the power off.
Caution! Turning the power on again may start the drive immediately.
The relevant fault code (see Diagnostics) flashes in the panel display until the fault is reset or the
display is "cleared".
You can "clear" the display without resetting the fault by pressing any button. The word FAULT will be
displayed.
Note! If no other button is pressed within 15 seconds and the fault is still active, the fault code
will be displayed again.
After a power failure, the drive will revert to the same control mode (LOC or REM) as before the
power failure.
ACS 400 User's Manual