Group 32: Supervision

Parameters of this group are used together with relay output parameters 1401
1402
2. Any two parameters within the Operating Data group (Group 1) can be
RELAY OUTPUT
supervised. Relays can be configured to be energized when the values of supervised parameters are
either too low or too high.
Code Description
3201 SUPERV 1 PARAM
First supervised parameter number within the Operating Data group (Group 01).
3202 SUPERV 1 LIM LO
First supervision limit low. Display of this parameter depends on selected supervised parameter (3201).
3203 SUPERV 1 LIM HI
First supervision limit high. Display of this parameter depends on selected supervised parameter (3201).
3204 SUPERV 2 PARAM
Second supervised parameter number within the Operating Data group (Group 01).
3205 SUPERV 2 LIM LO
Second supervision limit low. Display of this parameter depends on selected supervised parameter (3204).
3206 SUPERV 2 LIM HI
Second supervision limit high. Display of this parameter depends on selected supervised parameter (3204).
De-energized = 0
De-energized = 0
A = Parameter 1401
value is
B = Parameter 1401
2)value is
Figure 35 Operating data supervision using relay outputs.
82
hi (3203)
lo (3202)
Energized = 1
Energized = 1
RELAY OUTPUT
1
or
SUPRV
OVER
SUPRV
RELAY OUTPUT
1
or
SUPRV
UNDER
Value of supervised parameter
1 (1402
RELAY OUTPUT
2
OVER
1 (1402
RELAY OUTPUT
2
SUPRV
UNDER
1 and
RELAY OUTPUT
A
B
2)