Led Indicators; Resetting The Drive From The Control Panel - ABB ACS 400 User Manual

Speed control of 3 to 50 hp (2.2 to 37 kw) ac induction motors
Hide thumbs Also See for ACS 400:
Table of Contents

Advertisement

LED Indicators

Red LED
OFF
OFF
ON
BLINKS

Resetting the Drive from the Control Panel

When the red LED of the ACS-PAN is on or blinking, a fault is active.
To reset a fault when the red LED is on, press the RESET button.
Caution! This may start the drive, when in remote control.
To reset a fault when the red LED is blinking, turn the power off.
Caution! Turning the power on again may start the drive immediately.
The relevant fault code (see Diagnostics) flashes in the panel display until the fault is reset or the
display is "cleared".
You can "clear" the display without resetting the fault by pressing any button.
Note! If no other button is pressed within 15 seconds and the fault is still active, the fault code
will be displayed again.
After a power failure, the drive will revert to the same control mode (LOC or REM) as before the
power failure.
ACS 400 User's Guide
Green LED
ON
Power ON and drive is operating normally.
BLINKS
Alarm is active.
ON
Fault is active. Drive can be reset from the control panel.
ON
Fault is active. Turn power off to reset the drive.
29

Advertisement

Table of Contents
loading