Output signal source selection

It is possible to control both the relay outputs 1 and 2, as well as the analog output from the serial
communication channel 1.
Relay outputs can be controlled in the following way:
Step 1: Configure the ACS 400 to supervise the value of any of the parameters 131-133 using
parameters in group 32
Step 2: Configure a relay output 1 or 2 to respond to the status of one of the supervised parameter.
The selected relay can now be turned on or off by writing to supervised parameter (131-133) some
value that is either above or below the given supervision limits.
Refer to Table 15 for more information on required parameter settings. With the given settings,
writing any value 100 - 255 to parameter 131
Writing any value 0 - 99 to parameter 131 causes the relay output 1 to deactivate .
Refer to Table 16 for information on analog output control.
Table 15 Relay output control.
Code Parameter Name
Group 01
OPERATING DATA
0131
1
SER LINK DATA
0132
2
SER LINK DATA
Group 14
RELAY OUTPUTS
1401
1
RELAY OUTPUT
1402
2
RELAY OUTPUT
Group 32
SUPERVISION
3201
1
SUPERV
PARAM
3202
1
SUPERV
LIM LO
3203
1
SUPERV
LIM HI
3204
2
SUPERV
PARAM
3205
2
SUPERV
LIM LO
102
.
SUPERVISION
Alternative
Settings
0 - 255
0 - 255
NOT SEL
...
1
SUPRV
OVER
1
SUPRV
UNDER
2
SUPRV
OVER
2
SUPRV
UNDER
...
UNDERLOAD
As above
102 - 137
0 - 255
0 - 255
102 - 137
0 - 255
1 causes the relay output 1 to activate .
SER LINK DATA
Setting for
Standard
Function/Information
Modbus
-
Controlling data for the relay outputs.
-
e.g.
1
Relay output 1 function.
SUPERV
With the given setting, the relay 1 is
OVER
activated when supervised parameter 1
(given by parameter 3201) is above the
limit given by parameter 3203.
e.g.
1
Relay output 2 function.
SUPERV
See above.
OVER
e.g. 131
Number of supervised parameter 1. Any
parameter of the group 1 OPERATING
DATA.
e.g. 100
Lower supervision limit for supervised
parameter 1.
e.g. 100
Upper supervision limit for supervised
parameter 1.
e.g. 132
Number of supervised parameter 1. Any
parameter of the group 1 OPERATING
DATA.
e.g. 100
Lower supervision limit for supervised
parameter 2.
ACS 400 User's Manual