J Control Terminals
Main I/O terminal X1
The analog input signal is selected with V/I jumper J1: AI open = V and AI connected = I.
X1 Identification
1
SCR
Terminal for signal cable screen. (Connected internally to frame ground.)
2
AI 1
Analog input channel 1, programmable.
Default: 0 - 10 V (R
0 - 20 mA (R
Resolution 0.1 % accuracy ±1 %.
3
AGND
Analog input circuit common. (Connected internally to frame ground through 1 MΩ.)
4
10 V
10 V/10 mA reference voltage output for analog input potentiometer, accuracy ±2 %,.
5
AI 2
Analog input channel 2, programmable.
Default: 0 - 20 mA (R
0 - 10 V (R
Resolution 0.1 % accuracy ±1 %.
6
AGND
Analog input circuit common. (Connected internally to frame ground through 1 MΩ.)
Analog output, programmable. Default: 0-20 mA (load < 500 Ω) <=>0-f
7
AO1
8
AGND
Common for DI return signals.
9
24 V
Auxiliary voltage output 24 V DC / 250 mA (reference to AGND).
Short circuit protected.
Digital input common for DI1, DI2 and DI3. To activate a digital input, there must be ≥+10 V
10 DCOM1
(or ≤-10 V) between that input and DCOM1. The 24 V may be provided by the ACS 400
(X1:9) using the connection examples (see Section L) or by an external 12-24 V source of
either polarity.
DI Configuration
Factory (0)
(f
nom
11 DI 1
Start. Close to start. Motor will ramp up to
frequency reference. Open to stop. Motor will
coast to stop.
12 DI 2
Reverse. Close to reverse rotation direction.
13 DI 3
Jog. Close to set output frequency to jogging
frequency (default: 5 Hz).
14 DI 4
Must be closed for Factory (0).
15 DI 5
Accel/Decel selection (ACC1/DEC1 or ACC2/DEC2).
16 DCOM2
DCOM2 digital input common for DI4, DI5
17 RO1C
18 RO1A
19 RO1B
20 RO2C
21 RO2A
22 RO2B
Digital input impedance 1.5 k
Use multi-strand 0.5-1.5 mm
Note! DI 4 is read only when powered-up (Factory macro (0) and (1)).
Note! For safety reasons the fault relay signals a "fault" when the ACS 400 is powered
down.
14
= 200 kΩ) (J1:AI1 open) <=> 0 - f
i
= 500 Ω) (J1:AI1 closed) <=> 0 - f
i
= 500 Ω) (J1:AI2 closed) <=> 0 - f
i
= 200 kΩ) (J1:AI2 open) <=> 0 - f
i
= 50 Hz)
Relay output 1, programmable (default: fault => 17 connected to 18).
Relay output 2, programmable (default: running => 20 connected to 22).
.
2
(20-16 AWG) wire.
Description
frequency reference
nom
frequency reference
nom
frequency reference
nom
frequency reference
nom
Factory (1)
(f
= 60 Hz)
nom
Start. If DI 2 is closed, momentary closing
of DI 1 starts the ACS 400.
Stop. Momentary opening stops the
ACS 400.
Reverse. Close to reverse rotation
direction.
Must be open for Factory (1).
12 - 250 V AC / 30 V DC, 10 mA - 2 A
12 - 250 V AC / 30 V DC, 10 mA - 2 A
output frequency
nom
ACS 400 User's Manual