Acs 140 Basic Parameters - ABB ACS 140 Programming Manual

Hide thumbs Also See for ACS 140:
Table of Contents

Advertisement

ACS 140 Basic Parameters

ACS 140 has a large number of parameters. Of these, only the so called
basic parameters are initially visible.
Setting up only a few basic parameters is sufficient in applications where the
preprogrammed application macros of the ACS140 can provide all desired
functionality. For a full description of programmable features provided by the
ACS140, see "ACS 140 Complete Parameter List", starting page 23.
The following table lists the basic parameters.
S = Parameters can be modified only when the drive is stopped.
Code Name
Group 99
START-UP DATA
9902
APPLIC MACRO
Selects application macro.Sets parameter values to their default
values. Refer to "Application Macros", starting page 13 for detailed
description of each macro.
0 =
FACTORY MACRO
1 =
ABB STANDARD
2 = 3-
WIRE
3 =
ALTERNATE
Default value: 0 (
9905
MOTOR NOM VOLT
Nominal motor voltage from motor rating plate. Range of this
parameter depends on the type of the ACS 140 (200/400 V unit).
Selection for 200 V units:
200, 208, 220, 230, 240 V
Default value for 200 V unit: 230V
Default value for 400 V unit: 400 or 440V depending on selected
application macro.
9906
MOTOR NOM CURR
Nominal motor current from motor rating plate. Values for this
parameter range from 0.5* I
the ACS 140.
Default value: I
9907
MOTOR NOM FREQ
Nominal motor frequency from motor rating plate.
Range: 0 - 250.0 Hz
Default: 50.0 Hz or 60.0 Hz depending on selected application macro.
9908
MOTOR NOM SPEED
Nominal motor speed from motor rating plate.
Range 0 - 3600 rpm.
Default: 1440 or 1720 rpm depending on selected application macro.
4 =
MOTOR POT
5 =
HAND
6 =
PID CONTROL
7 =
PREMAGN
)
FACTORY MACRO
- 1.5* I
N
N
-
AUTO
Selection for 400V units:
380, 400, 415, 440, 460, 480 V
, where I
is nominal current of
N
N
The table continues on the next page .
User S
ä
ä
ä
ä
ä
9

Advertisement

Table of Contents
loading

Table of Contents