Application Macro ABB Standard

This general purpose macro provides two more preset speeds compared to Factory Macro (0).
Note! The value of parameter 9902 is 1 (
Input signals
• Start, stop and direction
(DI1,2)
• Analog reference (AI1)
• Preset speed selection (DI3,4)
• Ramp pair 1/2 selection (DI5)
*Constant speed selection: 0 = open, 1 = connected
ABB Standard parameter values:
9905
MOTOR NOM VOLT
9907
MOTOR NOM FREQ
9908
MOTOR NOM SPEED
1001
1
EXT
COMMANDS
1002
2
EXT
COMMANDS
1003
DIRECTION
1102
1/
EXT
EXT
1103
1
EXT REF
44
Output signals
• An. output AO: Frequency
• Relay output 1: Fault
• Relay output 2: Running
SCR
1
AI1
2
AGND
3
+10V
4
AI2
5
AGND
6
mA
AO1
7
AGND
8
+24V
9
DCOM1
10
DI1
11
DI2
12
DI3
13
DI4
14
DI5
15
DCOM2
16
RO1C
17
RO1A
18
RO1B
19
RO2C
20
RO2A
21
RO2B
22
DI3
DI4
0
0
1
0
0
1
1
1
400 V
50 Hz
1440 rpm
2 (
1,2)
DI
0 (
NOT SEL
3 (
REQUEST
2
6 (
SEL
EXT
1 (
1)
SELECT
AI
).
ABB STANDARD
External Reference 1: 0...10 V <=> 0...50 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...50 Hz
+24 VDC
Start/Stop: Activate to start
Fwd/Rev: Activate to reverse rotation direction
Constant speed selection*
Constant speed selection*
Ramp pair selection. Activate to select ramp pair 2.
Relay ouput 1, programmable
Default: Fault => 17 connected to 18
Relay ouput 2, programmable
Default: Running => 20 connected to 22
Output
Reference through AI1
Const speed 1 (1202)
Const speed 2 (1203)
Const speed 3 (1204)
1105
EXT REF
1106
EXT REF
1201
CONST SPEED SEL
1503
AO CONTENT MAX
)
1601
RUN ENABLE
)
1604
FAULT RESET SEL
2008
MAXIMUM FREQ
1)
2105
PREMAGN SEL
2201
/
ACC
DEC
V/I jumper S1
AI1:
0 -10 V
AI2:
0 -10 V
1
50 Hz
MAX
2
0 (
SELECT
KEYPAD
7 (
3,4)
DI
50 Hz
0 (
NOT SEL
0 (
KEYPAD
50 Hz
0 (
NOT SEL
1/2
5 (DI5)
SEL
ACS 400 User's Manual
)
)
)
)