ABB ACS 400 User Manual page 48

Speed control of 3 to 50 hp (2.2 to 37 kw) ac induction motors
Hide thumbs Also See for ACS 400:
Table of Contents

Advertisement

Code Name
9908 MOTOR NOM SPEED
Nominal motor speed from motor nameplate.
Range 0 - 3600 rpm
Default: 1440 or 1720 rpm depending on application macro selected.
9909 MOTOR NOM POWER
Nominal motor power from nameplate.
Range: 1 - 100 kW (1.5 - 125 Hp)
Default: 1 kW (1.5 Hp)
9910 MOTOR COS PHI
Nominal motor cos phi from nameplate.
Range: 0.50 - 0.99
Default: 0.83
Group 01
OPERATING DATA
0128 LAST FAULT
Last recorded fault (0 = no fault). See "Diagnostics", starting on page 35.
Can be cleared with the control panel by pressing UP and DOWN buttons
simultaneously when in parameter set mode.
Group 10
COMMAND INPUTS
1003 DIRECTION
Rotation direction lock.
1 =
FORWARD
2 =
REVERSE
3 =
REQUEST
If you select
REQUEST
Default: 3 (
REQUEST
Group 11
REFERENCE SELECT
1105
EXT REF1 MAX
Maximum frequency reference in Hz.
Range: 0 -250 Hz
Default value: 50 Hz or 60 Hz depending on the application macro selected.
Group 12
CONSTANT SPEEDS
1202 CONST SPEED 1
Range for all constant speeds: 0 - 250.0 Hz
Default value: 5.0 Hz
1203 CONST SPEED 2
Default value: 10.0 Hz
1204 CONST SPEED 3
Default value: 15.0 Hz
38
, the direction is set according to the given direction command.
) or 1 (
) depending on the application macro selected.
FORWARD
User
S
ACS 400 User's Guide