Communication settings

Communication settings define the communication speed, parity checking, number of stop bits and
fault functions. These settings for Channel 1 are defined using parameters in groups 50
COMMUNICATION and 52 STANDARD MODBUS.
Default communication settings for Channel 1 are listed in Table 12. To be able to communicate
with the master device, the ACS 400 must use the same communication speed and parity settings
as the master.
Further information on all parameters and their alternative settings is given in under "ACS 400
Complete Parameter List" on page 51.
Table 13 Communication parameters.
Code
Name
Group 52
STANDARD MODBUS
5201
STATION NUMBER
5202
COMM SPEED
5203
PARITY
Group 50
COMMUNICATION
5003
COMM FAULT TIME
5004
COMM FAULT FUNC
5005
PROTOCOL SEL
ACS 400 User's Manual
Range
Default
1 - 247
1
300,...,19200 bps
9600 bits/s
,
,
NONE
EVEN
ODD
NONE
0.1 - 60.0 s
1.0 s
,
,
NOT SEL
FAULT
NOT SEL
7,
CONST SP
LAST SPEED
,
,
NOT SEL
DDCS
STD
NOT SEL
,
MODBUS
STD
+
MDB
DDCS
User
Function/Information
Slave number for ACS
400 in Modbus network.
Communication speed.
Parity and stop bit setting.
Time limit for
communication loss
detection.
Operation in case
communication with the
master device is lost.
Communication protocols
selection.
Normally must be set to
.
STD MODBUS
99