INVERTER FR-HC2 INSTRUCTION MANUAL High power factor converter FR-HC2-7.5K to 75K FR-HC2-H7.5K to H560K OUTLINE INSTALLATION AND WIRING PARAMETERS PROTECTIVE FUNCTIONS MAINTENANCE AND INSPECTION SPECIFICATIONS...
Thank you for choosing the Mitsubishi High Power Factor Converter. This Instruction Manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the converter, please read this manual carefully to use the equipment to its optimum.
Page 3
(2) Trial run (6) Disposal CAUTION CAUTION Before starting the operation, each parameter must be The converter must be treated as industrial waste. confirmed and adjusted. A failure to do so may cause (7) General instruction some machines to make unexpected motions. Many of the diagrams and drawings in this Instruction ...
Terminal arrangement of the main circuit terminal ............... 28 2.6.3 Cable sizes of the main control circuit terminals and earth (ground) terminals ......31 Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K) ....... 34 2.7.1 Connection diagram (when using with the FR-A700 series) ............34 2.7.2 Wiring of main circuit ........................
Page 5
2.9.1 Connection diagram (when using with the FR-A700 series)............47 2.9.2 Wiring of main circuit ........................48 2.10 Notes on earthing (grounding)............53 2.11 Compatible inverter for the high power factor converter....54 2.11.1 Applicable inverter capacity ......................54 2.11.2 Inverter parameter settings......................55 2.12 Wiring of several inverters to one converter ........
Page 6
3.4.13 DU/PU, terminal FM/AM monitor display selection (Pr. 46 to Pr. 48, Pr. 50, Pr. 52, Pr. 54) ..86 3.4.14 Operation selection at instantaneous power failure (Pr. 57)............89 3.4.15 Free parameter (Pr. 58, Pr. 59) ....................90 3.4.16 Key lock selection of operation panel(Pr. 61) ................90 3.4.17 Retry function (Pr.
Page 7
SPECIFICATIONS Rated specifications ............... 148 Common specifications ..............149 Outline dimensions ................. 150 6.3.1 Converter (FR-HC2) ........................150 6.3.2 Reactor 1 (FR-HCL21)........................ 157 6.3.3 Reactor 2 (FR-HCL22)........................ 165 6.3.4 Difference between the reactor 1 (FR-HCL21) and the reactor 2 (FR-HCL22)......172 6.3.5 Outside box (FR-HCB2)......................
OUTLINE This chapter explains the "OUTLINE" for use of this product. Always read the instructions before using the equipment. Pre-operation instructions ............2 Converter and peripheral devices ..........7 Precautions for selecting peripheral devices ......8...
REMARKS Inverter parameters must be set. The parameter settings differ by the inverter series. Refer to page 55 for details. Power supply harmonic suppression effect (Example) FR-HC2-7.5K (Condition) Load: 100% Power factor: 1 [When the converter is not connected] [When the converter is connected]...
Page 10
Pre-operation instructions Application of the Harmonic Suppression Guideline for Specific Consumers Install, add or renew equipment Calculation of equivalent capacity total Equal to or less than reference capacity Equivalent capacity total Above reference capacity Calculation of outgoing harmonic current More than upper limit Not more than harmonic current upper limit?
Page 11
Pre-operation instructions Table 5 Rated Capacity and Outgoing Harmonic Current during Inverter Run Rated Current Fundamental Harmonic Current Converted from 6.6kV (mA) Applied Rated Wave Current (No reactor, 100% operation ratio) Motor Capacity Converted from (kW) (kVA) 200V 400V 11th 13th 17th 19th...
(Refer to the instruction manual of options.) Front cover (Refer to page 16) Combed shaped wiring cover Capacity plate Rating plate Rating plate Capacity plate FR-HC2-7.5K Converter model name FR-HC2-7.5K Converter model name Serial number Applicable inverter capacity Input rating Rated output Serial number...
Page 13
Always install the included peripheral devices. Check the model name of the each peripheral device. For the 400V class peripheral devices, H is indicated in front of the model name. FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K Peripheral Device Description...
Converter and peripheral devices Converter and peripheral devices Three-phase AC power supply Use within the permissible power supply specifications of the converter. Moulded case circuit breaker (MCCB) or earth leakage current breaker (ELB), fuse The breaker must be selected carefully since an inrush current flows in the converter at power ON.
Precautions for selecting peripheral devices Precautions for selecting peripheral devices 1.3.1 Measures against noises (EMI) In this section, noises indicate those of more than 40th to 50th high frequencies in a power distribution system, which generally assume irregular conditions. Some noises enter the converter to adversely affect it, and others are radiated by the converter to adversely affect peripheral devices.
Precautions for selecting peripheral devices Noise Measures Transmission Path When the devices, which handle low-level signals and are susceptible to noises (such as measuring instruments, receivers and sensors), are installed near or in the same enclosure with the converter, or their signal cables are placed near of in the same enclosure with the converter, the devices may malfunction due to air-propagated electromagnetic noises.
Page 17
Precautions for selecting peripheral devices (4) Using options to suppress noises By using the radio noise filter (FR-BIF) and the line noise filter (FR-BLF), the noise radiated from the connection cable can be suppressed. Refer to the Instruction Manual of each option for the detail of the radio noise filter (FR-BIF) and the line noise filter (FR-BLF).
Check the model of the converter and select peripheral devices according to the capacity. Refer to the table below to prepare appropriate peripheral devices. 200V class Moulded Case Circuit Breaker (MCCB) Magnetic Contactor Converter Model or Earth Leakage Circuit Breaker (ELB) (MC) (NF, NV type) FR-HC2-7.5K S-N25 FR-HC2-15K S-N50 FR-HC2-30K 150A S-N80 FR-HC2-55K 300A S-N180 FR-HC2-75K 350A S-N300 400V class...
Page 19
Precautions for selecting peripheral devices (2) Fuse Installation of a fuse is recommended between a high power factor converter and an inverter. Select a fuse according to the capacity of the connected motor. When using a motor, of which the capacity is smaller than the inverter capacity by two ranks or more, select the fuse with the capacity that is one rank lower than the inverter capacity.
Page 20
Precautions for selecting peripheral devices 400V class Motor Recommended fuse Fuse rating (A) Model Fuse holder (2 poles) capacity (kW) 12.5 6.900 CP GR 10.38 0012.5 0.75 6.900 CP GR 10.38 0016 US102 (without fuse light melting indicator) 6.900 CP GR 10.38 0016 or US102I (with fuse light melting indicator) 6.900 CP GR 10.38 0020...
Precautions for selecting peripheral devices 1.3.3 Selecting the rated sensitivity current for the earth leakage circuit breaker When using the earth leakage circuit breaker with the inverter circuit, select its rated sensitivity current as follows. Breaker for harmonic and surge lg1, lg2, lg3 : leakage current of cable path during ...
Protruding the heatsink..............21 Installation of peripheral devices ..........23 Main circuit terminal specifications ..........27 Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K).................... 34 Wiring of main circuit (FR-HC2-H280K) ........41 Wiring of main circuit (FR-HC2-H400K, H560K) ......47 2.10 Notes on earthing (grounding) ............
Removal and installation of the converter (FR-HC2) front cover Removal and installation of the converter (FR-HC2) front cover Removal of the operation panel 2) Push the left and right hooks of the operation panel and pull 1) Loosen the two fixed screws on the operation panel. the operation panel toward you to remove.
Page 24
Removal and installation of the converter (FR-HC2) front cover 30K or higher Removal 1) Loosen the installation screws of 2) Loosen the installation screw of 3) Push the two installation hooks on the right to the front cover 1, and remove the the front cover 2.
Removal and installation of the outside box (FR-HCB2) front cover Removal and installation of the outside box (FR-HCB2) front cover Removal 1) Loosen the installation screws of the front cover. 2) For removal, pull off the front cover. Front cover Front cover Reinstallation 1) Securely press the front cover...
Installation Installation Incorrect installation and connection may cause the equipment to operate improperly and its lifespan to be reduced considerably. Please handle the unit properly in accordance with the information on each section as well as the precautions in this manual. 2.3.1 Converter placement Installation of the converter...
Page 27
Installation (2) Clearances around the converter To ensure ease of heat radiation and maintenance, leave at least the shown clearance around the converter. At least the following clearance are required under the converter as a wiring space, and above the converter as a heat radiation space. Surrounding air temperature and humidity Clearance (front) Clearance (side)
When using a heatsink protrusion attachment (FR-A7CN) For the FR-HC2-7.5K to 75K and FR-HC2-H7.5K to H110K, a heatsink can be protruded outside the enclosure using a heatsink protrusion attachment (FR-A7CN). (For the 160K or higher, the attachment is not necessary when the heatsink is to be protruded.)
Page 29
Protruding the heatsink (2) Moving and removing the back installation frames FR-HC2-H160K to H280K Shift Upper One installation frame is attached to each of the upper and lower parts installation frame of the converter. Change the position of the rear side installation frame on the upper and lower sides of the converter to the front side as shown on the right.
Installation of peripheral devices Installation of peripheral devices 2.5.1 Installation of reactor 1 and reactor 2 Model name confirmation Take caution as the appearances of the reactor 1 (FR-HCL21) and the reactor 2 (FR-HCL22) are very similar. Reactor 1(FR-HCL21) AC REACTOR MODEL FR-HCL21-XXX SERIAL XXXXX...
Installation of peripheral devices (5) Installation orientation To prevent looseness, install the reactor 1 (FR-HCL21) and the reactor 2 (FR-HCL22) on a horizontal surface securely with screws or bolts. Do not install them on a vertical wall. Install them on a mounting stand which can withstand their weight. NOTE Since the charged sections of the reactor 1 and the reactor 2 are uncovered, fully protect them to prevent ground fault and electric shock.
Installation of peripheral devices 2.5.3 Installation of filter capacitor (FR-HCC2-H280K to H560K) Clearance Because the filter capacitor (FR-HCC2) generates heat, leave sufficient space around it. 10cm or more 10cm or more 10cm or more Installation place Install the filter capacitor on nonflammable material. Direct installation on a flammable material will cause a fire. Environment Avoid places where the equipment is subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Installation of peripheral devices (3) Environment Avoid places where the equipment is subjected to oil mist, flammable gases, fluff, dust, dirt, etc. Install the equipment in a clean place or protect it from suspended substances. Do not place a flammable material near the equipment. (4) Installation orientation To prevent looseness, install the inrush current limit resistor (FR-HCR2) on a horizontal or vertical surface securely with screws or bolts.
Main circuit terminal specifications Main circuit terminal specifications 2.6.1 Description of main circuit terminal Terminal Terminal Name Description Symbol These terminals are used to detect power phase and power voltage, and to input control R/L1, S/L2, T/L3 Power input power. Connect them to the commercial power supply. If the inverter is operated without connecting them to the commercial power supply, the converter will be damaged.
Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K) Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K) Perform wiring securely to conform with the harmonic suppression guideline of the former Ministry of International Trade and Industry (currently the Japanese Ministry of Economy, Trade and Industry). Incorrect wiring causes the converter to display an alarm or causes an fault or damage.
Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K) NOTE • When connecting the converter to the inverter, match the control logic (sink logic (initial setting)/source logic). The converter does not operate properly if the control logic is different.
Page 43
Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K) (2) Wiring of reactor 1 and outside box • Cable size differs by the capacity. Select an appropriate cable by referring to 2.6.3 Cable sizes of the main control circuit terminals and earth (ground) terminals (refer to page 31) and perform wiring.
Page 44
Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K) Wiring of outside box and reactor 2 • Cable size differs by capacity. Select an appropriate cable by referring to 2.6.3 Cable sizes of the main control circuit terminals and earth (ground) terminals (refer to page 31) and perform wiring.
Page 45
Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K) (5) Wiring of high power factor converter and inverter • These units should be connected to transmit commands from the high power factor converter to the inverter securely. Connection method differs depending on the inverter series. Refer to the Instruction Manual of the inverter when connecting.
Page 46
Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K) Wiring reactor 1 and converter Supply power to the power detecting terminals (R/L1, S/L2, T/L3) separately from the main circuit wiring. <Wiring example of 7.5K> Converter Reactor 1 Reactor 1...
Page 47
Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K) (8) Wiring of outside box and high power factor converter Use the cable shown in the below table for the connection. Cable gauge 0.75 to 1.25mm Converter terminals ROH and SD are used for the control signal for the inrush current limit circuit inside the outside box.
Wiring of main circuit (FR-HC2-H280K) Wiring of main circuit (FR-HC2-H280K) Perform wiring securely to conform with the harmonic suppression guideline of the former Ministry of International Trade and Industry (currently the Japanese Ministry of Economy, Trade and Industry). Incorrect wiring causes the converter to display an alarm or causes an fault or damage.
Page 49
Wiring of main circuit (FR-HC2-H280K) NOTE • When connecting the converter to the inverter, match the control logic (sink logic (initial setting)/source logic). The converter does not operate properly if the control logic is different. (Refer to page 60 for the switching of the control logic. Refer to the Instruction Manual of the inverter for the switching of the control logic of the inverter.) •...
Wiring of main circuit (FR-HC2-H280K) 2.8.2 Wiring of main circuit Wiring power supply and reactor 1 Use the cable shown in the below table for the connection. Cable gauge 200mm Use the moulded case circuit breaker (MCCB), the earth leakage circuit breaker (ELB) or the magnetic contactor (MC) shown in the below table.
Page 51
Wiring of main circuit (FR-HC2-H280K) 1) Filter capacitor Install three filter capacitors in parallel to the output side of the reactor 1 or to the input side of the inrush current limit MC as shown in the above diagram. Use the cable shown in the table below for the connection of filter capacitor. Cable gauge 60mm Wiring length...
Page 52
Wiring of main circuit (FR-HC2-H280K) Wiring example of converter and inverter These units should be connected to transmit commands from the converter to the inverter securely. Connection method differs depending on the inverter series. Refer to the Instruction Manual of the inverter when connecting.
Page 53
Wiring of main circuit (FR-HC2-H280K) (6) Wiring the power supply and inverter Connect the inverter control power supply directly to the power supply without connecting a converter in between. R1/L11 Inverter control S1/L21 power supply MCCB Power supply Cable gauge 0.75 to 2mm NOTE ...
Wiring of main circuit (FR-HC2-H400K, H560K) Wiring of main circuit (FR-HC2-H400K, H560K) Perform wiring securely to conform with the harmonic suppression guideline of the former Ministry of International Trade and Industry (currently the Japanese Ministry of Economy, Trade and Industry). Incorrect wiring causes the converter to display an alarm or causes an fault or damage.
Wiring of main circuit (FR-HC2-H400K, H560K) NOTE • When connecting the converter to the inverter, match the control logic (sink logic (initial setting)/source logic). The converter does not operate properly if the control logic is different. (Refer to page 60 for the switching of the control logic. Refer to the Instruction Manual of the inverter for the switching of the control logic of the inverter.) •...
Page 56
Wiring of main circuit (FR-HC2-H400K, H560K) Wiring reactor 1, filter capacitor, limit resistor, inrush current limit MC, and reactor 2 <Wiring example of 400K> Limit MC1 Reactor 1 Reactor 2 Converter (FR-HCL21-H400K) (FR-HC2-H400K) (FR-HCL22-H400K) To inverter FR-HCC2-H400K FR-HCC2-H400K 1)Filter capacitors 2 Limit MC2 Filter capacitor alarm detector (NC contact) 2 Buffer relay for...
Page 57
Wiring of main circuit (FR-HC2-H400K, H560K) 1) Filter capacitor Install filter capacitors to the output side of the reactor 1 or to the input side of the inrush current limit MC as shown in the connection diagram on page 49. Connect two units in parallel for 400K, and three units in parallel for 560K.
Page 58
Wiring of main circuit (FR-HC2-H400K, H560K) Wiring example of converter and inverter These units should be connected to transmit commands from the converter to the inverter securely. Connection method differs depending on the inverter series. Refer to the Instruction Manual of the inverter when connecting.
Page 59
Wiring of main circuit (FR-HC2-H400K, H560K) (6) Wiring the power supply and inverter Connect the inverter control power supply directly to the power supply without connecting a converter in between. R1/L11 Inverter control S1/L21 power supply MCCB Power supply Cable gauge 0.75 to 2mm NOTE ...
Notes on earthing (grounding) 2.10 Notes on earthing (grounding) Always earth (ground) the converter with its accessories (reactor 1, reactor 2, outside box, filter capacitor). (1) Purpose of earthing (grounding) Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before use. An electrical circuit is usually insulated by an insulating material and encased.
Compatible inverter for the high power factor converter 2.11.2 Inverter parameter settings When using the converter with the inverter, some inverter parameters must be set. The parameter settings differ by the inverter series. For the parameters and inverters not listed below, refer to the Instruction Manual of the inverter. V/F control Other than V/F control Inverter series...
Wiring of several inverters to one converter 2.12 Wiring of several inverters to one converter Up to ten inverters can be connected to one converter. Be sure to use a converter with the capacity higher than the total capacities of inverters. Additionally, the total capacity of the inverters needs to be higher than half the converter capacity. If the total inverter capacity is less than half the converter capacity, the converter can be used as a common converter or a regenerative converter.
Page 64
Wiring of several inverters to one converter Example of control circuit wiring INV1 FR-HC2 A720 INV2 A720 INV3 For the control circuit wiring, use shielded or twisted A720 5.5K wires, and separate the wire from the main circuit and high-voltage circuits. Keep the total wiring length within 30m.
Wiring of control circuit 2.13 Wiring of control circuit 2.13.1 Description of control circuit terminal indicates that terminal functions can be selected using Pr. 3 to Pr. 7 (input terminal function selection) and Pr. 11 to Pr. 16 (output terminal function selection)(Refer to page 76, 78) (1) Input signal Terminal Type...
Page 66
Wiring of control circuit Output signal Terminal Type Terminal Name Description Rated Specifications Symbol Turns ON at alarm occurrence and reset (RES) signal input. Connect this terminal to the terminal MRS or a terminal where Inverter run enable the X10 signal is assigned to in the inverter. signal Turning ON RDY signal stops the inverter.
Wiring of control circuit 2.13.2 Changing the control logic The input signals are set to sink logic (SINK) when shipped from the factory. To change the control logic, the jumper connector on the back of the control terminal must be moved to the other position. (The output signals may be used in either the sink or source logic independently of the jumper connector position.) (1) Loosen the two installation screws at the both side of the control circuit terminal block.
Page 68
Wiring of control circuit (4) Sink logic and source logic In the sink logic, a signal switches ON when a current flows from the corresponding signal input terminal. Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals. In the source logic, a signal switches ON when a current flows into the corresponding signal input terminal.
Wiring of control circuit 2.13.3 Control circuit terminal layout Dedicated board for FR-HC2 Terminal screw size: M3 Terminals 5, IRH, IRL, TR1, TR2, IRO, MCO, RDO, RDI, and MCI are for manufacturer setting. Keep them open. 88R 88S NC AM M3.5 Terminal screw size: (1) Common terminals of the control circuit (SD, 5, SE, SE2)
Wiring of control circuit Signal inputs by contactless switches The contacted input terminals of the converter (RES, SOF, X1, X2, ROH) +24V can be controlled using a transistor instead of a contacted switch as shown on the right. RES, etc Converter External signal input using transistor 2.13.4 Wiring instructions...
Wiring of control circuit 2.13.5 When connecting the operation panel or parameter unit using a connection cable Having an operation panel on the enclosure surface is convenient. With a connection cable, you can mount the operation panel (FR-DU07-CNV) or parameter unit (FR-PU07) to the enclosure surface, and connect it to the converter. Use the option FR-CB2, or the following connector and cable available on the market.
PARAMETERS This chapter provides the "PARAMETERS" of this product. Always read the instructions before using the equipment. Operation panel (FR-DU07-CNV) ..........66 Parameter unit (FR-PU07), parameter unit with battery pack (FR-PU07BB(-L))................69 Parameter list ................73 Description of parameters ............75 Parameter clear / All parameter clear..........
Operation panel (FR-DU07-CNV) Operation panel (FR-DU07-CNV) 3.1.1 Names and functions of the operation panel (FR-DU07-CNV) Operation mode indicator P.CPY: Flickers at the completion of parameter copy. OFF at converter reset. PWR : Lit at power ON Power / regenerative drive indicator DRIVE: Lit during power driving REGEN: Lit during regenerative driving (DRIVE or REGEN flickers when a stop is...
Operation panel (FR-DU07-CNV) 3.1.2 Basic operation (factory setting) Monitor mode (Input current monitor) Input voltage monitor Bus voltage monitor Display the present Parameter setting mode setting (Example) Value change Parameter and a setting value flicker alternately. Parameter write is completed!! Parameter clear All parameter Faults clear...
Operation panel (FR-DU07-CNV) 3.1.3 Changing the parameter setting value Changing example Change the Pr. 3 ROH terminal function selection setting. Operation Display Screen at power-ON The monitor display appears. The parameter Press to choose the parameter number read setting mode. previously appears.
Parameter unit (FR-PU07), parameter unit with battery pack (FR-PU07BB(-L)) Parameter unit (FR-PU07), parameter unit with battery pack (FR-PU07BB(-L)) Parameter setting and monitor display can be performed by connecting the parameter unit (FR-PU07) or the parameter unit with battery pack (FR-PU07BB(-L)) to the converter. Note that their functions are limited compared to when they are used with the inverter.
Parameter unit (FR-PU07), parameter unit with battery pack (FR-PU07BB(-L)) 3.2.3 Monitoring function (1) Monitor display overview (f) Warning indication I In 10.0 (a) Main monitor (e) Unit indication (b) Connection phase sequence indication (d) Operation mode indication (c) Operating status indication a) Main monitor Shows the input frequency, input current, bus voltage, fault history and other monitor data.
Parameter unit (FR-PU07), parameter unit with battery pack (FR-PU07BB(-L)) 3.2.4 Function menu Press in any operation mode to call the function menu, on which you can perform various functions. REMARKS Some menus are not available. Function menu list Function menu Description 1.
Page 79
Parameter unit (FR-PU07), parameter unit with battery pack (FR-PU07BB(-L)) 3 Pr.List 1 Setting Mode SETTING MODE 1 Appl.Grp 0~9:Ser Pr.No. 2 Pr.List 2 Pr.List 3 Set Pr.List 3 User List Select Oper 4 Param Copy 4 Def.Pr.List Pr Mode Max.F Min.F 3 Pr.List ROH Sel...
Parameter list Parameter list REMARKS indicates simple mode parameters. The parameters shaded in allow their settings to be changed during operation even if "1" (write disabled) is set to Pr. 77 Parameter write selection. Initial Refer to Customer Parameter Name Range Increments...
Page 81
Parameter list Initial Refer to Customer Parameter Name Range Increments value page setting Rated 0.01A/ 56 Current monitoring reference 0 to 500A/0 to 3600A current 0.1A 57 Restart selection 0, 9999 9999 Free parameter 1 0 to 9999 9999 Free parameter 2 0 to 9999...
Description of parameters Description of parameters 3.4.1 Displaying and hiding extended parameters (Pr. 0) Parameter which can be read from the operation panel and parameter unit can be restricted. Parameter Name Initial Value Setting Range Description Number Only the simple mode parameters can be 9999 displayed.
Description of parameters 3.4.3 Input terminal function selection (Pr. 3 to Pr. 7) Use the following parameters to select/change the input terminal functions. Parameter Initial Setting Name Initial Signal Number Value Range ROH terminal function selection ROH (ROH inrush resistance overheat detection) SOF terminal function selection SOF (converter stop) X1 terminal function selection...
Description of parameters 3.4.4 Operation selection of SOF signal and OH signal (Pr. 8, Pr. 9) Operation of SOF signal can be changed by the Pr. 8 setting, and OH signal by the Pr. 9 setting. Parameter Initial Setting Name Description Number Value...
Description of parameters 3.4.5 Output terminal function selection (Pr. 10 to Pr. 16) Use the following parameters to change the functions of the open collector output terminals and relay output terminal. Parameter Initial Name Initial Signal Setting Range Number Value RDY signal logic selection RDY (Inverter run enable signal) 0, 100...
Description of parameters 3.4.6 DC voltage control (Pr. 22 to Pr. 24, Pr. 80, Pr. 81) DC voltage of the converter can be controlled to be as commanded. Operation should be stable in the initial setting, but adjust the following parameters when voltage fluctuation occurs due to the environment such as a voltage condition.
Description of parameters 3.4.7 Input current detection function (Y12 signal, Y13 signal, Pr. 25 to Pr. 30) The input current during converter running can be detected and output to the output terminal. Parameter Initial Name Setting Range Description Number Value Set the input current detection level.
Description of parameters 3.4.8 Displaying the life of the converter parts (Pr. 31 to Pr. 33) Degrees of deterioration of control circuit capacitor, cooling fan and inrush current limit circuit can be diagnosed by the monitor. When any part has approached the end of its life, an alarm can be output by self diagnosis to prevent a fault. (Use the life check of this function as a guideline since the life is calculated theoretically.) Parameter Setting...
Description of parameters (2) Life display of the inrush current limit circuit (Pr. 32) The life of the inrush current limit circuit (relay, contactor and inrush resistor) is displayed in Pr. 32. The number of contact (relay, contactor, thyristor) ON times is counted, and it is counted down from 100% (0 time) every 1%/1,000 times.
Description of parameters 3.4.10 Cooling fan operation selection (Pr. 36) Cooling fans built into the converter can be controlled. Parameter Initial Setting Name Description Number Value Range A cooling fan operates at power ON. Cooling fan ON/OFF control is invalid. (The cooling fan is always ON at power ON) Cooling fan operation selection Cooling fan ON/OFF control is valid.
Description of parameters 3.4.12 Reference of the terminal FM (pulse train output) and terminal AM (analog output) (Pr. 45, Pr. 49, Pr. 51, Pr. 53, Pr. 55, Pr. 56) Two types of monitor output, pulse train output from the terminal FM and analog voltage output from the terminal AM, are available.
Page 92
Description of parameters Reference for input power monitor (Pr. 51), input voltage monitor (Pr. 53), bus voltage monitor (Pr. 55), and current monitor (Pr. 56). For the calibration of terminal FM, set the full-scale value of the connected meter when the pulse speed of terminal FM is 1440 pulse/s.
Description of parameters 3.4.13 DU/PU, terminal FM/AM monitor display selection (Pr. 46 to Pr. 48, Pr. 50, Pr. 52, Pr. 54) The monitor to be displayed on the main screen of the operation panel (FR-DU07-CNV)/parameter unit (FR-PU07) can be selected. In addition, signals to be output from the terminal FM (pulse train output) and AM (analog voltage output) can be selected.
Page 94
Description of parameters Pr. 52 Setting Full-scale Pr. 54 (FM) Value of the Types of Monitor Increments Pr. 50 (AM) Description Terminal FM DU LED main Setting and AM monitor Depends on Depends on Monitoring item is changed by ON/OFF of Switching by input terminal 1111 to 4444 the monitor...
Page 95
Description of parameters (3) Cumulative power monitor and clear (Pr. 46, Pr. 48) On the cumulative power monitor (Pr. 52 = "8"), the input power is accumulated and updated in 100ms increments. (The value is stored in EEPROM every 1h.) ...
Description of parameters Monitor switching with input terminal (Pr. 50, Pr. 52, Pr. 54) Monitoring item can be switched by ON/OFF of terminals X1 and X2. By setting 1 to 4 to the four digits of Pr. 52 (Pr. 54, Pr. 50), monitor can be switched by the terminals. Number set in each digits represents the following monitor.
Description of parameters 3.4.15 Free parameter (Pr. 58, Pr. 59) You can input any number within the setting range of 0 to 9999. For example, the number can be used: As a unit number when multiple units are used. ...
Description of parameters 3.4.17 Retry function (Pr. 65, Pr. 67 to Pr. 69) If a fault occurs, the converter resets itself automatically to restart. Fault-activating retries can be also selected. Parameter Name Initial value Setting range Description Number A fault for retry can be selected. (Refer to the Retry selection 0 to 4 table in the next page.)
Description of parameters Using Pr. 65, you can select the fault that will cause a retry. No retry will be made for the fault not indicated. (Refer to page 126 for the fault description. ) indicates the faults selected for retry. Fault for Pr.
Page 100
Description of parameters Reset selection You can select the enable condition of reset function (RES signal, reset command through communication) input. When Pr. 75 is set to any of "1, 3, 15, 17", a reset can be input only when the converter is tripped. NOTE ...
Description of parameters 3.4.19 Parameter write disable selection (Pr. 77) You can select whether to enable the writing to various parameters or not. Use this function to prevent parameter values from being rewritten by misoperation. Parameter Name Initial Value Setting Range Description Number Parameter write is disabled.
Description of parameters 3.4.20 Current control (Pr. 82, Pr. 83) This function controls current to be as commanded. Operation should be stable in the initial setting, but adjust the following parameters when current fluctuation occurs due to the environment such as power source condition. Parameter Initial Name...
Description of parameters (2) Wiring and configuration of PU connector communication system System configuration Station 0 Computer Station 0 Computer Converter Converter Converter RS-232C FR-DU07-CNV Operation connector panel RS-485 RS-232C Maximum connector connector connector connector interface/ cable FR-ADP terminals RS-232C-RS-485 (option) converter...
Description of parameters 3.4.22 Initial settings and specifications of RS-485 communication (Pr. 117 to Pr. 124) This function is used to perform required settings for RS-485 communication between the converter and personal computer. Use PU connector of the converter for communication. You can perform parameter setting, monitoring, etc.
Description of parameters 3.4.23 Mitsubishi inverter protocol (computer link communication) You can perform parameter setting, monitoring, etc. from the PU connector of the converter using the Mitsubishi inverter protocol (computer link communication). (1) Communication The communication specifications are given below. Related Item Description...
Page 106
Description of parameters Communication operation presence/absence and data format types Data communication between the computer and converter is made in ASCII code (hexadecimal code). Communication operation presence/absence and data format types are as follows. Parameter/ Converter Parameter Operation Monitor Monitor Reset...
Page 107
Description of parameters Data reading format Communication request data from the computer to the converter 1) Number of Characters Format Station number Instruction code check Reply data from the converter to the computer 3) (No data error detected) Number of Characters Format Station number...
Page 108
Description of parameters Data definitions 1) Control code Signal ASCII Code Description Name Start Of Text (Start of data) End Of Text (End of data) Enquiry (Communication request) Acknowledge (No data error detected) Line Feed Carriage Return Negative Acknowledge (Data error detected) 2) Station number Specify the station number of the converter which communicates with the computer.
Page 109
Description of parameters 7) Error code If any error is found in the data received by the converter, its error definition is sent back to the computer together with the NAK code. Error Error Item Error Description Converter Operation Code The number of errors consecutively detected in communication Computer NAK error request data from the computer is greater than permissible...
Page 110
Description of parameters Retry count setting (Pr. 121) Set the permissible number of retries at data receive error occurrence. (Refer to page 102 for data receive error for retry.) If data receive errors occur consecutively and exceed the permissible number of retries set, the converter outputs the alarm (LF).
Page 111
Description of parameters (7) Instructions for the program 1) When data from the computer has any error, the converter does not accept that data. Hence, in the user program, always insert a retry program for data error. 2) All data communication, e.g. run command or monitoring, are started when the computer gives a communication request.
Page 112
Description of parameters General flowchart Port open Communication setting Time out setting Send data processing Data setting Sum code calculation Data transmission Receive data waiting Receive data processing Data retrieval Screen display CAUTION Always set the communication check time interval before starting operation to prevent hazardous conditions. Data communication is not started automatically but is made only once when the computer provides a communication request.
Page 113
Description of parameters (8) Setting items and set data After completion of parameter settings, set the instruction codes and data, then start communication from the computer to allow various types of operation control and monitoring. Number of Read/ Instruction Item Data Description Data Digits Write...
Page 114
Description of parameters Number of Read/ Instruction Item Data Description Data Digits Write code (Format) All parameters return to the initial settings. Whether to clear communication parameters or not can be selected according to the data. (: Clear, : Not clear) Refer to page 188 for parameter clear, all clear, and communication parameters.
Page 115
Description of parameters [Special monitor selection No.] Refer to page 86 for details of the monitor description. Data Description Increments Data Description Increments Data Description Increments H01 Input current 0.01A/0.1A 0.01kW/ 0.1kW/ H07 Input power H0A Input power H02 Input voltage 0.1V 0.1kW ...
Description of parameters 3.4.24 Initial setting and specification for the CC-Link communication function (Pr. 542 to Pr. 544) Set the station number and baud rate required for the CC-Link communication. Parameter Initial Name Setting range Description Number value Communication station 1 to 64 Set the station number of the converter.
Page 117
Description of parameters (3) CC-Link extended setting (Pr. 544) The functions of the remote register can be extended. Refer to page 110 for the details of the remote I/O signals and the remote registers. Pr. 544 Setting Description CC-Link Ver. 0 (Initial setting) Occupies one station (FR-A5NC compatible) ...
Page 118
Description of parameters 2)Remote register (For the details, refer to page 113.) I/O signals when one station (FR-A5NC compatible) in the CC-Link Ver.1 is occupied. (Pr. 544 = "0") Description Description Device No. Device No. Upper 8 Bits Lower 8 Bits Upper 8 Bits Lower 8 Bits RWwn...
Page 119
Description of parameters (5) Details of the remote I/O signals The following device numbers are for the station number 1. For the station number 2 and later, the device numbers are different. (Refer to the manual for the CC-Link master module for the correspondence between device numbers and stations numbers.) Output signals (master module ...
Page 120
Description of parameters Details of the remote register The following device numbers are for the station number 1. For the station number 2 and later, the device numbers are different. (Refer to the manual for the CC-Link master module for the correspondence between device numbers and station numbers.) Remote register (master module ...
Page 121
Description of parameters (7) Instruction code definition Operation control and monitoring can be performed through CC-Link communication by setting the following instruction codes and corresponding data after setting parameters. Set instruction codes using the remote register (RWw). (Refer to page 113) Definitions read by instruction codes are stored in the remote register (RWr).
Description of parameters 3.4.25 Operation at a communication error (Pr. 500 to Pr. 502) Operation at a communication error in the CC-Link communication can be selected. Parameter Setting Name Initial value Description Number range Communication error Set the waiting time for the communication error output 500...
Description of parameters (3) Converter operation at a communication error (Pr. 502) How the converter operates at a communication line error or an option unit fault can be set. Setting description Operation at an error occurrence Fault description Pr. 502 Setting Converter operation Indication Fault output...
Description of parameters 3.4.27 Setting of the parameter unit and operation panel (Pr. 145, Pr. 990, Pr. 991) Setting of the operation panel and parameter unit can be changed. Parameter Name Initial Value Setting Range Description Number Japanese English German French PU display language selection Spanish...
Description of parameters 3.4.28 Terminal FM and AM calibration (calibration parameter C0 (Pr. 900), C1 (Pr. 901)) By using the operation panel or parameter unit, you can calibrate terminal FM and AM to full scale deflection. Parameter Name Initial Value Setting Range Description Number...
Page 126
Description of parameters AM terminal calibration (C1 (Pr. 901)) Converter Terminal AM is initially-set to provide a 10VDC output in the full-scale status of the corresponding monitor item. Calibration parameter C1 (Pr. 901) DC10V allows the output voltage ratios (gains) to be adjusted according to the meter scale.
Parameter clear / All parameter clear Parameter clear / All parameter clear POINT Set "1" to Pr. CL Parameter clear, ALLC All parameter clear to initialize all parameters. (Parameters are not cleared when Pr. 77 Parameter write selection = "1".) ...
Parameter copy and parameter verification Parameter copy and parameter verification PCPY Setting Description Cancel Copy the source parameters to the operation panel. Write the parameters copied to the operation panel into the destination converter. Verify parameters in the converter and operation panel. (Refer to page 122) REMARKS ...
Page 129
Parameter copy and parameter verification appears... Why? Parameter read error. Perform operation from step 3 again. appears... Why? Parameter write error. Perform operation from step 8 again. flicker alternately Appears when parameters are copied between the converter of or lower and or higher.
PROTECTIVE FUNCTIONS This chapter provides the "PROTECTIVE FUNCTIONS" of this product. Always read the instructions before using the equipment. Troubleshooting................124 Reset method of protective function .......... 124 List of fault and alarm indications..........125 Causes and corrective actions ............ 126 Correspondences between digital and actual characters ..
Troubleshooting Troubleshooting When a fault occurs in the converter, the protective function activates to trip the converter, and the PU display automatically changes to one of the following fault or alarm indications. If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales representative.
List of fault and alarm indications List of fault and alarm indications Operation Panel Indication Name Refer to page E- - - Faults history HOLD Operation panel lock Error Parameter write error message rE1 to 4 Copy operation fault Err. Error Overload signal detection PU stop...
Causes and corrective actions Causes and corrective actions (1) Error message A message regarding operational troubles is displayed. The converter continues its operation. Operation Panel HOLD Indication Name Operation panel lock Operation lock is set. Operation other than is invalid. Description (Refer to page 90) Checkpoint...
Page 134
Causes and corrective actions Operation Panel Indication Name Model error Parameter write or parameter verification of the parameter copy function is performed to an invalid model. Description When writing of copied parameters is attempted after reading of copied parameters is interrupted ...
Page 135
Causes and corrective actions Operation Panel FR-PU07 Indication Name Maintenance signal output Indicates that the cumulative energization time of the converter has reached a given time. Description When the setting of Pr. 35 Maintenance timer alarm output set time is the initial setting (Pr. 35 = "9999"), this warning does not occur.
Page 136
Causes and corrective actions Operation Panel E.OV2 FR-PU07 Stedy Spd OV Indication Name Overvoltage trip If the converter's internal main circuit DC voltage reaches or exceeds the specified value, the protective Description circuit is activated to stop the converter operation.The circuit may also be activated by a surge voltage produced in the power supply system.
Page 137
Causes and corrective actions Operation Panel E.ILF FR-PU07 Input phase loss Indication Name Input phase loss Description Converter trips when one phase of the three phase power input is lost. Checkpoint Check for a break in the cable for the three-phase power supply input. ...
Page 138
Causes and corrective actions Operation Panel E.PE FR-PU07 Corrupt Memry Indication Name Parameter storage device fault (control circuit board) Description Stops the converter operation if a fault occurred in the parameter stored. (EEPROM fault) Checkpoint Check for too many number of parameter write times. Please contact your sales representative.
Page 139
Causes and corrective actions Operation Panel FR-PU07 Fault 9 Indication Name Input power supply fault 2 When the converter operation is stopped continuously due to the fluctuation of input voltage or input current, Description it is regarded as a power supply fault, and the converter operation and the inverter output are stopped. Checkpoint Check the power source and the wiring.
Correspondences between digital and actual characters Operation Panel E.13 FR-PU07 Fault 13 Indication Name Internal circuit fault Description Stops the converter operation when an internal circuit fault occurs. Corrective action Please contact your sales representative. NOTE If faults other than the above appear, contact your sales representative. Correspondences between digital and actual characters There are the following correspondences between the actual alphanumeric characters and the digital characters displayed on the operation panel:...
Check and clear of the faults history Check and clear of the faults history (1) Check and clear of the faults history Monitor/frequency setting Parameter setting [Operation panel is used [Parameter setting change] for operation] Faults history [Operation for displaying faults history] Eight past faults can be displayed with the setting dial.
Page 142
Check and clear of the faults history Clearing procedure POINT Set Er.CL Fault history clear = "1" to clear the faults history. Display Operation Screen at power-ON The monitor display appears. The parameter Press to choose the parameter number previously setting mode.
Check first when you have a trouble Check first when you have a trouble Trouble Checkpoint Check the connection. Check if the wiring is performed correctly. Check if appropriate power supply voltage is applied. Converter does not operate properly. ...
MAINTENANCE AND INSPECTION This chapter provides "MAINTENANCE INSPECTION" of this product. Always read the instructions before using the equipment. Inspection items................138 Measurement of main circuit voltages, currents and powers .. 145...
Inspection items The converter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and vibration, changes in the parts with time, service life, and other factors.
Inspection items 5.1.3 Daily and periodic inspection list Interval Area of Corrective Action at Customer's Inspection Item Description Periodic Daily Inspection Alarm Occurrence Check Surrounding Check the surrounding air temperature, Improve the environment. environment humidity, dirt, corrosive gas, oil mist, etc. Check alarm location and Check for unusual vibration and noise.
Inspection items 5.1.4 Checking the converter module <Preparation> (1) Disconnect the external power supply cables (R4/L14, S4/L24, T4/L34, P/+, N/-) (2) Prepare a tester. (Use 100 range.) <Checking method> Change the polarity of the tester alternately at the converter terminals R4/L14, S4/L24, T4/L34, P/+, N/- and check the electric continuity.
When unusual noise and/or vibration are noticed during inspection, the cooling fan must be replaced immediately. NOTE For parts replacement, contact the nearest Mitsubishi FA center. Removal (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H110K) 1) Push the hooks from above and remove the fan cover. FR-HC2-7.5K, 15K FR-HC2-30K or higher FR-HC2-H7.5K, H15K...
Page 149
Inspection items Reinstallation (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H110K) 1)After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of "AIR FLOW" faces up. AIR FLOW <Fan side face> 2)Reconnect the fan connectors.
Page 150
Inspection items Removal (FR-HC2-H160K or higher) 1) Remove the fan cover. 2) Remove the fan connector, then remove the fan block. 3) Remove the fan fixing screws, then remove the fan. (Make sure to remove the fan cable from the clamp of the fan block beforehand.) Fan fixing screws Fan ∗...
Page 151
Inspection items (2) Smoothing capacitors A large-capacity aluminum electrolytic capacitor is used for smoothing in the main circuit DC section, and an aluminum electrolytic capacitor is used for stabilizing the control power in the control circuit. Their characteristics are deteriorated by the adverse effects of ripple currents, etc.
Measurement of main circuit voltages, currents and powers Measurement of main circuit voltages, currents and powers Measurement method of voltage and current at each section When instruments for commercial frequency are used for measurement, measure the following circuits with the instruments given below.
Measurement of main circuit voltages, currents and powers Measuring Points and Instruments Remarks Item Measuring Point Measuring Instrument (Reference Measured Value) Across R and S Commercial power supply Power supply voltage Across S and T Moving-iron type AC voltmeter Within permissible AC voltage Across T and R fluctuation (Refer to page 148) Power supply side current...
SPECIFICATIONS This chapter provides the "SPECIFICATIONS" of this product. Always read the instructions before using the equipment. Rated specifications ..............148 Common specifications ............... 149 Outline dimensions............... 150...
Common specifications Common specifications Control method PWM control Power supply frequency range 50Hz to 60Hz Current limit level Current limit value selectable (0 to 220% variable) The following signals can be assigned to Pr. 3 to Pr. 7 (input terminal function selection): Input signal (Five terminal) converter stop, monitor switching, converter reset, external thermal relay, and inrush resistance overheat detection.
Page 158
Outline dimensions FR-HC2-30K 2-φ10 hole 2-φ20 hole (102) Eybolt: 2-M8∗ P.CPY PWR REGEN ..DRIVE PSCLR Rating plate The eyebolt is enclosed with the product. Use it as required. (Unit: mm) Mass: 24kg FR-HC2-55K 2-φ20 hole 2-φ10 hole (150) Eybolt: 2-M8∗...
Page 159
Outline dimensions FR-HC2-75K 2-φ25 hole 2-φ12 hole (93) 2-φ25 hole Eyebolt : 2-M10∗ P.CPY PWR REGEN DRIVE PSCLR Rating plate The eyebolt is enclosed with the product. Use it as required. (Unit: mm) Mass: 53kg (2) 400V class FR-HC2-H7.5K, H15K 2-φ6 hole Rating plate (Unit: mm)
Page 160
Outline dimensions FR-HC2-H30K 2-φ10 hole 2-φ20 hole (102) Eyebolt: 2-M8∗ Rating plate The eyebolt is enclosed with the product. Use it as required. (Unit: mm) Mass: 26kg FR-HC2-H55K 2-φ10 hole 2-φ20 hole (142) Eyebolt: 2-M8∗ Rating plate The eyebolt is enclosed with the product.
Page 161
Outline dimensions FR-HC2-H75K 2-20 hole 2-10 hole (142) Eyebolt: 2-M8 P.CPY PWR REGEN ..DRIVE PSCLR Rating plate The eyebolt is enclosed with the product. Use it as required. (Unit: mm) Mass: 37kg FR-HC2-H110K φ 25 hole φ 25 hole φ...
Outline dimensions 6.3.2 Reactor 1 (FR-HCL21) Check that the capacity of the reactor 1 is same as the capacity of the converter. 200V class FR-HCL21-7.5K, 15K R/L1 S/L2 T/L3 Within D2 Rating plate W1 0.5 -2.5 Varnish removed area (front/rear side) 4-M6 hole Model Mass...
Page 165
Outline dimensions FR-HCL21-55K ∗Enlarged view of section A Rating plate Crimping terminal for 6-M12 screws (80-M12) Within 105 ∗A S/L2 T/L3 R/L1 -2.5 Within 210 (Unit: mm) Within 140 58 2.5 Mass: 17.4kg Varnish removed area (front/rear side) 4-M6 hole FR-HCL21-75K ∗Enlarged ∗Enlarged...
Page 166
Outline dimensions 400V class FR-HCL21-H7.5K 50 0.5 4-M6 hole -0.5 R/L1 S/L2 T/L3 Within 55 Rating plate (Unit: mm) Mass: 4kg Varnish removed area (front/rear side) FR-HCL21-H15K 4-M6 hole -0.5 R/L1 S/L2 T/L3 Within 65 Rating plate (Unit: mm) Mass: 6kg Varnish removed area (front/rear side)
Page 167
Outline dimensions FR-HCL21-H30K 75 0.5 4-M6 hole -0.5 R/L1 S/L2 T/L3 Within 95 Rating plate (Unit: mm) 99 2 Mass: 9kg Varnish removed area (front/rear side) FR-HCL21-H55K 8 0.5 4-M6 hole R/L1 S/L2 T/L3 (25) Within 70 Within 95 Varnish removed area (front/rear side) Rating plate (Unit: mm)
Page 168
Outline dimensions FR-HCL21-H75K ∗Enlarged ∗Enlarged view of view of section A section B Rating plate Approx. 20 75 1 Crimping terminal for 6-M10 screws (60-M10) S/L2 R/L1 T/L3 ∗A Earth (ground) terminal ∗B Approx. 9 (for M8 screw) 75 1 -2.5 (Unit: mm) 127 2...
Outline dimensions 6.3.3 Reactor 2 (FR-HCL22) Check that the capacity of the reactor 2 is same as the capacity of the converter. 200V class FR-HCL22-7.5K Varnish removed area (front side) MAX 140 (70) mark 210 1.5 110 1.5 (Unit: mm) 235 2.5 Mass: 9.8kg 4-M6 hole...
Page 173
Outline dimensions FR-HCL22-55K Varnish removed area (front side) MAX 280 430 2.5 (140) mark 270 1.5 240 1.5 (Unit: mm) Mass: 65kg 4-M8 hole FR-HCL22-75K Varnish removed area (front side) MAX 280 (190) mark (Unit: mm) 430 2 130 2 Mass: 98kg 470 4 4-M12 hole...
Page 174
Outline dimensions 400V class FR-HCL22-H7.5K 210 1.5 8 0.5 4-M6 hole MAX 70 MAX 70 Varnish removed area (front/rear side) (25) Rating plate (Unit: mm) Mass: 9.8kg 129 2.5 235 2.5 FR-HCL22-H15K 230 1.5 8 0.5 4-M6 hole MAX 75 MAX 90 Varnish removed area (front/rear side) (25)
Page 175
Outline dimensions FR-HCL22-H30K 310 1.5 10 0.5 4-M8 hole MAX 80 MAX 100 Varnish removed area (front/rear side) (30) Rating plate (Unit: mm) Mass: 36kg 153 2.5 340 2.5 FR-HCL22-H55K 360 1.5 10 0.5 4-M8 hole MAX 90 MAX 110 (30) Varnish removed area (front/rear side) Rating...
Page 176
Outline dimensions FR-HCL22-H75K UL mark (40) Varnish removed area (front side) MAX 280 MAX 430 (160) (Recommended 265 1.5 4-M10 (φ12 0.5) hole installation 200) 200 1.5 (Unit: mm) Mass: 120kg FR-HCL22-H110K UL mark Varnish removed area (front side) (50) MAX 370 (215) MAX 500...
Page 177
Outline dimensions FR-HCL22-H160K, H220K ULmark (75) Varnish removed area MAX D (front side) MAX D2 (Recommended 400 1.5 4-M12 ( 15 0.5) hole installation D1) MAX W Model Mass FR-HCL22-H160K 250kg FR-HCL22-H220K 345kg (Unit: mm) FR-HCL22-H280K UL mark Varnish removed area MAX 560 (front side) (355)
Page 178
Outline dimensions FR-HCL22-H400K 4-M12 eyebolt 2- 15 hole 500 5 for M12 screw 300 5 R4, S4, T4 side R3, S3, T3 side 100 5 R3/L13 R4/L14 S3/L23 S4/L24 T3/L33 T4/L34 Earth (ground) terminal (for M8 screw) 400 2 630 2 435 10 Within Within...
Outline dimensions 6.3.4 Difference between the reactor 1 (FR-HCL21) and the reactor 2 (FR-HCL22). Each reactor has a rating plate. Identify the reactor 1 and the reactor 2 by their rating plates. Incorrect connection order of the reactor 1 and the reactor 2 causes the reactors to heat up, and it is dangerous. Take caution to avoid the danger. [Rating plate] Reactor 1(FR-HCL21) AC REACTOR...
Page 180
Outline dimensions FR-HCB2-30K, 55K 2-A hole Rating plate Type A hole dimensions Model Mass FR-HCB2-30K 11kg FR-HCB2-55K 13kg (Unit: mm) FR-HCB2-75K 4-φ16 hole 3-A hole Rating plate Type A hole dimensions (Unit: mm) Mass: 27kg...
Page 181
Outline dimensions 400V class FR-HCB2-H7.5K to H30K 2-A hole Rating plate Type A hole dimensions (Unit: mm) Mass: 8kg FR-HCB2-H55K 2-A hole Rating plate Type A hole dimensions (Unit: mm) Mass: 16kg...
Page 182
Outline dimensions FR-HCB2-H75K 2-A hole Rating plate Type A hole dimensions (Unit: mm) Mass: 16kg FR-HCB2-H110K 3-A hole 4-φ16 hole Rating plate Type A hole dimensions (Unit: mm) Mass: 37kg...
Page 183
Outline dimensions FR-HCB2-H160K, H220K 4-φ16 hole 3-A hole Rating plate Type A hole dimensions (Unit: mm) Mass: 54kg...
Outline dimensions Filter capacitor alarm detector (MDA-1) (FR-HCC2-H400K, H560K) 150 3 Plunger Case Reference value as some margins are taken for the arm Micro switch Screw(M4) Connector Switch terminal and contact symbol of the detector 53 2 15 1 4-M4 5.6 (Unit: mm) 40 2 Screw with toothed...
Page 189
Outline dimensions Contactor (S-N400FXYS AC200V 2A2B) (FR-HCM2-H400K, H560K) (4-M8 hole) M4 screw (self-up) 4-M8 hole (60) (Unit: mm) M12 screw M4 screw (with washer and (self-up) Mass: 9.5kg spring washer) MC power supply stepdown transformer (BKO-CA2001H06) (FR-HCM2-H280K to H560K) Enlarged drawing of installation hole Terminal block for tap switching M4 screw Input side terminal block...
Page 190
Outline dimensions Terminal block shorting conductor (C152C481H21) (FR-HCM2-H280K) 80 0.4 60 0.4 40 0.4 5-oval 7-8 20 0.3 (2.3) Sectional view of A - A (Unit: mm) Mass: 0.1kg MC shorting conductor (C152C423H21) (FR-HCM2-H400K, H560K) (Unit: mm) 9-M5 screw for installation of Mass: 1.6kg 57.5...
Page 191
Outline dimensions Mini relay for filter capacitor alarm detector (MYQ4Z AC200/220) (FR-HCM2-H400K, H560K) 21.5 or less φ 1.2 2.2 oval hole 28 or less 28 or less 35.5 or less 21.5 or less (Unit: mm) Mass: 35kg Mini relay terminal block (PYF14T) (FR-HCM2-H400K, H560K) 23.5 33 or lower 11.5...
APPENDICES This chapter provides the "APPENDICES" of this product. Always read the instructions before using the equipment. Appendix 1 Instruction code list............188 Appendix 2 Instructions for compliance with the EU Directives..189 Appendix 3 Instructions for UL and cUL ..........191...
Appendix 1 Instruction code list These instruction codes are used to write or read parameters through the RS-485 communication and the CC-Link communication. (Refer to page 98 for the RS-485 communication. Refer to page 109 for the CC-Link communication.) ...
CE marking. The authorized representative in the EU The authorized representative in the EU is shown below. Name: Mitsubishi Electric Europe B.V. Address: Gothaer Strasse 8, 40880 Ratingen, Germany Note We declare that this converter, when equipped with the dedicated EMC filter, conforms with the EMC Directive in industrial environments and affix the CE marking on the inverter.
Page 197
Provide the Class T fuse or a fuse with faster shutoff speed, which is UL and cUL listed, for branch circuit protection. Converter model Fuse type Cat. No Manufacturer Rating FR-HC2-7.5K UL Recognized High Speed 170M1414 Bussmann 50A, 700 Vac FR-HC2-15K...
For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code and any applicable provincial codes. Provide the appropriate fuse in accordance with the table below. Converter model Fuse type Cat. No Manufacturer Rating FR-HC2-7.5K UL Recognized High Speed 170M1414 Bussmann 50A, 700 Vac FR-HC2-15K UL Recognized High Speed 170M1416...
Page 201
Mini relay terminal block (PYF14T) Mini relay clip (PYC-A1) Jul. 2010 IB(NA)-0600381ENG-C Addition FR-HC2-7.5K to 75K Pr. 44 Instantaneous power failure detection signal clear Monitored item: input power (with regenerative display) Output signal: Instantaneous power failure detection hold (Y16) Modification ...
Page 202
Additional notes for Instructions for UL and cUL General precaution CAUTION - Risk of Electric Shock - The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes. ATTENTION - Risque de choc électrique - La durée de décharge du condensateur de bus est de 10 minutes.
Page 203
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN IB(NA)-0600381ENG-F (1211)MEE Printed in Japan Specifications subject to change without notice.