5.29 COPY FUNCTION

The standard digital operator JVOP-140 of the V7 can be used to store (upload) parameters from one
drive, and copy (download) parameters to another drive. The copy function is not available on the
V74X. Parameters are stored in an EEPROM on the digital operator therefore no backup power supply
is necessary. The copy function can be used in most cases except the following.
(1) Different drive types – The user may not copy parameters from a V7 to a J7 drive.
(2) Different voltage class – The user may not copy parameters from a 230V drive to a 460V drive.
(3) Different control mode – The user may not copy parameters from a drive operating in the Volts per
The following parameters are not copied when capacities are different.
Parameter No.
Parameter Name
n011 to n017
V/f Settings
n036
Motor Rated Current
n080
Carrier Frequency
n105
Torque Comp Iron Loss
n106
Motor Rated Slip
n107
Motor Line-to-line Resistance
Parameters n176, n177, n178 and n179 are not read into the digital operator during a read command.
n176: Parameter Copy Function Selection
Setting
Description
rdy
Drive is ready to use Copy Function
rEd
Read (or upload) all parameters from the drive and store them in the Digital Operator
Cpy
Copy (or download) all parameters stored in the Digital Operator to the drive
uFy
Verify that parameters stored in the Digital Operator and the drive are the same
uA
Displays the voltage and kW rating of the drive whose parameters are stored in the
Digital Operator
Sno
Displays the software number of the drive whose parameters are stored in the Digital
Operator
arameter Copy Access Selection
n177:
P
Setting
Description
0
Copying Disabled
1
Copying Allowed
The Copy Function can be enabled or disabled using parameter n177 – parameters cannot be
uploaded when this parameter is disabled (n177 = 0), preventing the accidental overwriting of
parameters stored in the Digital Operator.
If n177 = 0 and an upload is attempted (n176 = rEd or Cpy), a "PrE" error message will blink on the
Digital Operator display – press DSPL or DATA/ENTER to clear the message.
hertz mode (n002=0) to a drive in the Open loop vector mode (n002=1).
Parameter No.
5-46
Parameter Name
n108
Motor Leakage Inductance
n109
Torque Boost
n110
Motor No-load Current
n140
Energy Saving Gain K2
n158
Motor Code (Energy Saving)
Factory Setting: rdy
Factory Setting: 0
Range: 0 or 1