N101 - YASKAWA V7 Technical Manual

Hide thumbs Also See for V7:
Table of Contents

Advertisement

PARA-
METER
NAME
Accel/Decel Time
n018
Setting Unit
n019
Acceleration Time 1 (Note 4)
n020
Deceleration Time 1 (Note 4)
n021
Acceleration Time 2 (Note 4)
n022
Deceleration Time 2 (Note 4)
n023
S-curve Selection
n024
Frequency Reference 1 (Note 4)
n025
Frequency Reference 2 (Note 4)
n026
Frequency Reference 3 (Note 4)
n027
Frequency Reference 4 (Note 4)
n028
Frequency Reference 5 (Note 4)
n029
Frequency Reference 6 (Note 4)
n030
Frequency Reference 7 (Note 4)
n031
Frequency Reference 8 (Note 4)
n032
Jog Frequency Reference (Note 4)
Frequency Reference Upper
n033
Limit
Frequency Reference Lower
n034
Limit
Digital Operator
n035
Display Mode
n036
Motor Rated Current
Electronic Thermal Overload
n037
Protection (for OL1 fault)
Electronic Thermal Overload
n038
Protection Time Constant
Cooling Fan Operation
n039
Selection
n040
Motor Rotation
Acceleration Time 3
n041
(Note 4)
Deceleration Time 3
n042
(Note 4)
Acceleration Time 4
n043
(Note 4)
Deceleration Time 4
n044
(Note 4)
n050
Multi-function Input
Selection 1 (Terminal S1)
Multi-function Input
n051
Selection 2 (Terminal S2)
Multi-function Input
n052
Selection 3 (Terminal S3)
Table A1-1. Drive Parameters - Continued
SETTING RANGE
(AND UNITS)
0:
0.1
1:
0.01
0.00 to 600.0
or
0.0 to 6000
(Dependent on n018 setting)
0:
No S-curve
1:
0.2 second
2:
0.5 second
3:
1.0 second
0.00 to 400.00
0. to 110
0. to 110
0:
0.01 Hz (less than 100 Hz) / 0.1 Hz
1:
0.1%
2 - 39: rpm
40 - 3999: custom
0.1 to 49.5
(Up to 150% of drive rated current)
0:
Short term rating
1:
Standard rating
2:
Disabled
1 to 60
0:
Operates only when drive is running
(continues operation for 1 minute after
drive is stopped)
1:
Operates with power applied to drive
0:
Rotate C.C.W.
1:
Rotate C.W. (or opposite direction)
0.00 to 600.00
or
0.0 to 6000.0
(Dependent on n018 setting)
0:
Fwd / Rev command (3 wire control)
[can only be set in n052]
1:
Forward run (2 wire control)
2:
Reverse run (2 wire control)
3:
External Fault (N.O.)
1
4:
External Fault (N.C.)
5:
Fault Reset
6:
Multi-step speed ref. cmd. A
7:
Multi-step speed ref. cmd. B
8:
Multi-step speed ref. cmd. C
A1-2
SETTING
FACTORY
USER
INCREMENT
SETTING
SETTING
1 (sec)
0
0.01 (sec)
or
10.0
0.1 (sec)
1
0
6.00
0.00
0.01 (Hz)
0.00
(< 100 Hz)
0.00
or
0.00
0.1 (Hz)
0.00
(>= 100 Hz)
0.00
0.00
6.00
1(%)
100
1(%)
0
1
0
0.1 (A)
(Note 1)
1
0
1 (min)
8
1
0
1
0
0.01 (sec)
or
10.0
0.1 (sec)
1
1
(1)
2
(2)
1
3
(0)
PARA.
REF.
5.2
5.2
5.3
5.11
5.12
5.9
5.30
5.25
5.25
5.2
5.18