5.27 V/f PATTERN

The V/f pattern can be tailored to suit your specific application and load characteristics by adjusting
parameters n011 to n017 (see the V/f characteristics figure on the following page).
Max.
Starting
Freq.
Torque
50
Normal
2
50
High
60
Normal
2
60
High
50
Normal
50
Medium
2
50
High
60
Normal
60
Medium
2
60
High
72
Normal
90
Normal
120
Normal
180
Normal
NOTES:
1
VT = Variable Torque, typically used for blowers, centrifugal pumps, and fans.
CT = Constant Torque, most other applications. Consult the manufacturer for further assistance.
The following conditions must be considered when selecting a V/f pattern:
- Pattern matches the voltage-frequency characteristics of the motor.
- Maximum motor speed.
2
V/f pattern for high starting torque should be selected for:
- Long wiring distance.
- Large voltage drop at start
- AC reactor connected to Drive input or output.
- Use of motor rated below Drive max. output.
3
Voltages shown are for 230V motors; for other motor voltages, multiply all voltage (V) values by (Vmtr/230).
i.e., for a 460V motor, multiply by 460/230 = 2.
Table 5-4. Recommended V/f Patterns
Load
n011
n012
1
Type
(Hz)
(V)
VT
50
230
VT
50
230
VT
60
230
VT
60
230
CT
50
230
CT
50
230
CT
50
230
CT
60
230
CT
60
230
CT
60
230
CT
72
230
CT
90
230
CT
120
230
CT
180
230
n013
n014
3
(Hz)
(Hz)
50
25.0
50
25.0
60
30.0
60
30.0
50
3.0
50
2.5
50
2.5
60
3.0
60
3.0
60
3.0
60
3.0
60
3.0
60
3.0
60
3.0
5-40
n015
n016
n017
3
(V)
(Hz)
(V)
40.2
1.3
9.2
57.5
1.3
11.5
40.2
1.5
9.2
57.5
1.5
11.5
17.2
1.5
11.5
23.0
1.3
13.8
28.7
1.3
16.1
17.2
1.5
11.5
20.7
1.5
13.8
28.7
1.5
23.0
17.2
1.5
11.5
17.2
1.5
11.5
17.2
1.5
11.5
17.2
1.5
11.5
3