5.4 AUTO-RESTART

n082 : Number of Auto-Restart Attempts
When a fault occurs during operation, the Drive can be programmed for an auto-restart operation to
automatically reset the fault. Auto-restart operation will use the number of reset attempts set in this
parameter, up to the maximum of 10. When set to " 0 ", no auto-restarts will be attempted.
Fault contact will not actuate (change state) during auto-restart attempts.
• The following faults can be automatically reset:
oC:
Overcurrent
ou:
Overvoltage (OV)
• The number of restart attempts available will be reset to the n082 setting when:
1. 10 minutes has elapsed without a fault occurring.
2. The RESET key, or external Fault Reset push button, is pressed.
3. Power is removed from the Drive.

5.5 CARRIER FREQUENCY

n080 : Carrier Frequency
The relationship between output frequency and carrier frequency is determined from the set value
of n080 .
(a) For constant carrier frequency, set to " 1 ", " 2 ", " 3 ", " 4 ".
(b) For synchronous mode, set n080 to " 7 ", " 8 ", or " 9 ". These setting values
establish carrier frequencies of 12f, 24f, or 36f, respectively.
CARRIER FREQUENCY(kHz)
n080
SETTING
Maximum(Fc
1
2.5
2
5.0
3
7.5
4
10.0
7
2.5
8
2.5
9
2.5
CARRIER
FREQUENCY
)
Minimum(Fc
)
MAX
MIN
2.5
5.0
7.5
10.0
1.0
1.0
1.0
Fc
MAX
Fc
MIN
0
F1
OUTPUT FREQUENCY
5-4
Factory setting: 0
Range: 0 - 10
Factory Setting: 3
Range: 1 to 4; 7 to 9
SLOPE
OUTPUT FREQUENCY(Hz)
(=Fc)
F1
Fo
0
NA
0
NA
0
NA
0
NA
12
83.3
24
41.6
36
27.7
SLOPE
F2
MODE
F2
NA
CONSTANT
NA
NA
NA
208.3
SYNCHRONOUS
104.1
69.4