5.24 STOPPING METHOD

n005 : Stopping Method
Selects the stopping method suitable for the application.
Setting
A.
Data 0 : Deceleration to Stop
Upon removal of the FWD (REV) Run
command, the motor decelerates at the
deceleration rate determined by the time
set in Decel Time 1 (n020 ), and DC
injection braking is applied immediately
before stop. If the decel time is too short
or the load inertia is too large, an over-
voltage (OV) fault may occur on a stop
command — the decel time must be
increased.
B.
Data 1 : Coast to Stop
Upon removal of the FWD (REV) Run command, the motor coasts to rest.
Output Frequency
Run Command
0
Deceleration (ramp) to stop
1
Coast to stop
Output Frequency
Min. Output Frequency
(Frequency at DC Injection
Braking Start) (n016 )
ON
5-37
Description
ON
Run Command
Drive output is shut OFF
when stop command is input
OFF
Factory setting: 0
Range: 0 to 1
Decel Time 1
(n020 )
DC Injection Braking
Time at Stop (n090 )
(Factory setting: 0.5 s)
OFF