Still Pipe/Chamber Installations - Emerson Rosemount 5408 Reference Manual

Level transmitters non-contacting radar
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Figure 3-8:
H
A.
B.
Table 3-7:
Nozzle size (D)
Pipe schedule std, Ø 8 in. (200 mm)
Pipe schedule std, Ø10 in. (250 mm)
(1) Note that the inside of the nozzle must be smooth (i.e. avoid bad welding, rust, or deposit).
3.3.8

Still pipe/chamber installations

Installation in still pipe/chamber is recommended for tanks where there are excessive
foaming or turbulence. Still pipe/chamber may also be used to avoid disturbing objects in
the tank.
Still pipe
Consider the following still pipe requirements:
Rosemount 5408 and 5408:SIS Level Transmitters
Mounting of the Parabolic Antenna
A
D
Nozzle mounting
Flange mounting in manhole cover
Nozzle Requirements for Parabolic Antenna, in Inches (Millimeters)
H
Ø 8 in. (200 mm)
Inclination angle (α)
Maximum nozzle height (H)
5.9 (150)
5.5 (140)
1.6 (40)
1.2 (30)
12°
1.0 (25)
15°
0.6 (15)
8.0 (200)
8.0 (200)
8.0 (200)
8.0 (200)
12°
5.9 (150)
15°
4.3 (110)
Mechanical Installation
B
(1)
21