Table 7-6:
Incorrect Level Readings
(1)
Symptom
Measured level is correct at 0% (4 mA) but
incorrect at 100% (20 mA).
Incorrect level when the product surface is
above the 50% level.
Measured value drops to zero level.
Rosemount 5408 and 5408:SIS Level Transmitters
(continued)
Possible causes
Upper Range Value is not set
correctly.
Time
Strong double bounce echo
that is interpreted as the
product surface.
Time
Transmitter has locked on a
strong tank bottom echo.
Time
Service and Troubleshooting
Recommended actions
Check that the Upper Range Value match-
es the 100% (20 mA) level in the tank.
Enable the Double Bounce Handling func-
tion, see
Section
7.5.4.
Verify the Reference Height is config-
ured correctly.
Enable the Tank Bottom Projection
function, see
Use tank bottom
projection.
Enable the Bottom echo visible when
tank is empty parameter, see
Enable bottom echo visible when tank is
empty.