Rosemount 3300 Series
Mounting a Centering
Disc for Pipe
Installations
3-20
Flexible Single/Twin Lead probe
Centering disc
Tab washer
Bolt
Tab washer
Rigid Single Lead probe
Bushing
Split pin
NOTE!
Centering discs may not be used with PTFE covered probes.
00809-0100-4811, Rev CA
1. Mount the centering disc at the
end of the weight.
2. Make sure that the tab washer is
properly inserted in the centering
disc.
Weight
3. Fasten the centering disc with
the bolt.
4. Secure the bolt by folding the tab
washer.
NOTE!
Centering discs made of PTFE must
not be used with the Rosemount 3300
HTHP version.
1. Mount the centering disc at the
end of the probe.
2. Fasten the disc by inserting the
split pin through the bushing
and the probe.
3. Secure the split pin.
Reference Manual
February 2006