Commissioning
NOTICE
NEGATIVE FEEDBACK
If the feedback is negative, the encoder connection is
wrong. Use either parameter 5-71 Term 32/33 Encoder
Direction or parameter 17-60 Feedback Direction to
inverse the direction, or reverse the encoder cables.
Parameter 17-60 Feedback Direction is only available with
®
the VLT
Encoder Input MCB 102 option.

6.6 System Start-up

WARNING
MOTOR START
6
6
Failure to ensure that the motor, system, and any
attached equipment are ready for start can result in
personal injury or equipment damage. Before start,
Ensure that equipment is safe to operate under
any condition.
Ensure that the motor, system, and any
attached equipment are ready for start.
The procedure in this section requires user-wiring and
application programming to be completed. The following
procedure is recommended after application set-up is
completed.
1.
Press [Auto On].
2.
Apply an external run command.
Examples of external run commands are a switch,
button, or programmable logic controller (PLC).
3.
Adjust the speed reference throughout the speed
range.
4.
Ensure that the system is working as intended by
checking sound and vibration level of the motor.
5.
Remove the external run command.
If warnings or alarms occur, see chapter 8.5 List of Warnings
and Alarms.

6.7 Parameter Settings

NOTICE
REGIONAL SETTINGS
Some parameters have different default settings for
international or North America. For a list of the different
default values, see chapter 10.2 International/North
American Default Parameter Settings.
Establishing the correct programming for applications
requires setting several parameter functions. Details for
parameters are provided in the programming guide.
52
VLT® AQUA Drive FC 202
Parameter settings are stored internally in the drive,
allowing the following advantages:
6.7.1 Uploading and Downloading
The drive operates using parameters stored on the control
card, which is located within the drive. The upload and
download functions move the parameters between the
control card and the LCP.
1.
2.
3.
4.
5.
6.7.2 Restoring Factory Default Settings
NOTICE
LOSS OF DATA
Loss of programming, motor data, localization, and
monitoring records occurs when restoring default
settings. To create a back-up, upload data to the LCP
before initialization. Refer to chapter 6.7.1 Uploading and
Downloading Parameter Settings.
Restore the default parameter settings by initializing the
unit. Initialization is carried out through
parameter 14-22 Operation Mode or manually.
Danfoss A/S © 01/2017 All rights reserved.
Parameter settings can be uploaded into the LCP
memory and stored as a back-up.
Multiple units can be programmed quickly by
connecting the LCP to the unit and downloading
the stored parameter settings.
Settings that are stored in the LCP are not
changed when restoring factory default settings.
Changes made to default settings as well as any
programming entered into parameters are stored
and available for viewing in the quick menu. See
chapter 6.3 LCP Menu.
Parameter Settings
Press [Off].
Go to parameter 0-50 LCP Copy and press [OK].
Select 1 of the following:
3a
To upload data from the control card to
the LCP, select [1] All to LCP.
3b
To download data from the LCP to the
control card, select [2] All from LCP.
Press [OK]. A progress bar shows the uploading or
downloading process.
Press [Hand On] or [Auto On].
MG22A102