Commissioning
4.
Select Q3-21 Analog Reference and press [OK].
14.7%
Open Loop Settings
Q3-20 Digital Reference
Q3-21 Analog Reference
Illustration 6.5 Q3-21 Analog Reference
Select parameter 3-02 Minimum Reference.
5.
Set the minimum internal drive reference to 0 Hz
and press [OK].
14.7%
Analog Reference
3-02 Minimum Reference
0.000 Hz
Illustration 6.6 Parameter 3-02 Minimum Reference
6.
Select parameter 3-03 Maximum Reference.
Set the maximum internal drive reference to
60 Hz and press [OK].
14.7%
Analog Reference
3-03 Maximum Reference
50.000 Hz
Illustration 6.7 Parameter 3-03 Maximum Reference
MG22A102
Operating Guide
0.00A
1(1)
Q3-2
0.00A
1(1)
Q3-21
0.00A
1(1)
Q3-21
Danfoss A/S © 01/2017 All rights reserved.
7.
Select parameter 6-10 Terminal 53 Low Voltage.
Set the minimum external voltage reference on
terminal 53 at 0 V and press [OK].
14.7%
0.00A
Analog Reference
6-10 Terminal 53 Low
Voltage
0.00 V
Illustration 6.8 Parameter 6-10 Terminal 53 Low Voltage
8.
Select parameter 6-11 Terminal 53 High Voltage.
Set maximum external voltage reference on
terminal 53 at 10 V and press [OK].
14.7%
0.00A
Analog Reference
6-11 Terminal 53 High
Voltage
10.00 V
Illustration 6.9 Parameter 6-11 Terminal 53 High Voltage
9.
Select parameter 6-14 Terminal 53 Low Ref./Feedb.
Value. Set minimum speed reference on terminal
53 at 20 Hz and press [OK].
14.7 %
Analog Reference
6 - 14 Terminal 53 Low
Ref./Feedb. Value
000020.000
Illustration 6.10 Parameter 6-14 Terminal 53 Low Ref./Feedb.
Value
1(1)
Q3-21
1(1)
Q3-21
0.00 A
1(1)
Q3-21
49